Plan Review Notes
Plan Review Notes For Permit 03072336
Permit Number 03072336
Review Stop E
Sequence Number 1
Notes
Date Text
2003-08-21 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SEE RISER FOR TENNIS CTS.
 PLEASE CLARIFY AND SHOW HOW EXIST 100A
 PANEL IS BEING FED? SHOWS 400A DISC AND
 THAT APPEARS TO FEED SOMETHING ELSE?
  
 2)NOTE: PLEASE PROVIDE ENGINEERING UNDER
 FBC FOR NEW LT POLES. 140MPH
  
 3)NOTE: PLEASE SEE EXISTING SERVICE FOR
 PRESS BOX/BATHS. PLEASE SEE LINE AND
 LOADS IN SAME ENCLOSURE, ETC ETC
 LOAD CALCS INCOMPLETE, PANEL SCHEDULE
 AND RISER DIAGRAM DO NOT CORRELATE.
 SHOWS 200A AND 100A ETC. 215.5/240/230
 ETC. PLEASE SEE CHAPTER 34 OF FBC FOR
 BRINGING EXIST ELEC UP TO CODE.
 4)NOTE: PLEASE SEE RECEPTS IN BATHS TO
 BE GFI. 210.8
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 THAT MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]