Plan Review Notes For Permit 03072336 |
Permit Number |
03072336 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-08-21 00:00:00 | **************** UNSAT *************** | | | | 1)NOTE: PLEASE SEE RISER FOR TENNIS CTS. | | PLEASE CLARIFY AND SHOW HOW EXIST 100A | | PANEL IS BEING FED? SHOWS 400A DISC AND | | THAT APPEARS TO FEED SOMETHING ELSE? | | | | 2)NOTE: PLEASE PROVIDE ENGINEERING UNDER | | FBC FOR NEW LT POLES. 140MPH | | | | 3)NOTE: PLEASE SEE EXISTING SERVICE FOR | | PRESS BOX/BATHS. PLEASE SEE LINE AND | | LOADS IN SAME ENCLOSURE, ETC ETC | | LOAD CALCS INCOMPLETE, PANEL SCHEDULE | | AND RISER DIAGRAM DO NOT CORRELATE. | | SHOWS 200A AND 100A ETC. 215.5/240/230 | | ETC. PLEASE SEE CHAPTER 34 OF FBC FOR | | BRINGING EXIST ELEC UP TO CODE. | | 4)NOTE: PLEASE SEE RECEPTS IN BATHS TO | | BE GFI. 210.8 | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | THAT MAY AFFECT ELECTRICAL PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE NAY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|