Plan Review Notes
Plan Review Notes For Permit 03072255
Permit Number 03072255
Review Stop B
Sequence Number 2
Notes
Date Text
2003-09-03 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SUBMIT A SIGNED AND SEALED COPY OF
 THE SOIL BORING TEST REPORT AS REQUIRED
 BY FBC 1804.2.2.
  
 3) REVISE GLASS BLOCK NOTE #5 ON A12.
 THE GLASS BLOCK IS REQUIRED TO HAVE A
 UNIFORM FACE THICKNESS OF 0.25 INCH WHEN
 LOCATED WITHIN (3) FEET HORIZONTALLY OF
 THE STANDING OR WALKING SURFACE OF A
 BATH TUB, SHOWER, ETC. SEE FBC 2405.2.1
 AND 2405.2.2.
  
 4) THE "REDLINE" CHANGE TO THE NEGATIVE
 WIND LOAD PRESSURE FOR THE DOUBLE ENTRY
 DOORS ON THE WIND LOAD SCHEDULE ON A1 IS
 REQUIRED TO BE INITIALED AND DATED BY
 THE DESIGNER OF RECORD.
  
 5) THE SITE SPECIFIC ENGINEERING DOES
 NOT NOT MEET THE WIND LOAD PRESSURES
 REQUIRED IN THE SCHEDULE ON A1 FOR THE
 DOUBLE GLAZED FRENCH DOORS.
  
 6) THE FRENCH DOORS ARE LISTED AS (2)
 3080 DOORS ON THE SCHEDULE ON A1 AND AS
 (2) 21080 DOORS ON A5. PLEASE CORRECT.
  
 7)SUBMIT A SIGNED AND SEALED COPY OF THE
 LETTER FROM KENEZEVICH AND ASSOCIATES
 ADDRESSING THE CALK-IN ANCHORS USE IN
 CONCRETE BLOCK. THE LETTER SHOULD ALSO
 INDICATE THE PSI OF THE BLOCK AS TESTED.
  
 8) PROVIDE ADDITIONAL INFORMATION ON THE
 INSERT HEADER AT THE COVERED LANAI.
 SPECIFY HOW IT WILL BE ANCHORED FOR
 UPLIFT, HOW THE TRUSSES WILL BE ATTACHED
 TO THE HEADER, HOW THE HEADER WILL BEAR
 ON THE WALL AT EACH END, ETC.
  
 IF YOU HAVE QUESTIONS, PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714