2003-08-19 00:00:00 | DENIED |
| |
| 1)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) SUBMIT A SOIL BORING TEST REPORT AS |
| REQUIRED BY FBC 1804.2.2. |
| |
| 4) THE GLASS BLOCK IN THE MASTER BATH |
| AND BATH 2 ARE IN HAZARDOUS LOCATIONS |
| AND ARE REQUIRED TO BE TEMPERED OR HAVE |
| A UNIFORM FACE THICKNESS OF 0.25 INCH |
| PER FBC 2405.2. |
| |
| 5) THE FULL BATH ON THE FIRST FLOOR IS |
| REQUIRED TO HAVE A DOOR WITH A 29" CLEAR |
| OPENING PER FBC 11-4.23.2. |
| |
| 6) FBC 1609.4 NO LONGER ALLOWS A ONE- |
| THIRD INCREASE IN THE STEEL CALCULATIONS |
| FOR COMBINATION LOADS. PLEASE REVISE THE |
| VALUES LISTED IN THE ANCHOR SCHEDULES ON |
| SHEETS A7 AND A8 TO VALUES THAT DO NOT |
| INCLUDE THIS INCREASE. SEE THE 2003 USP |
| CATALOG. |
| |
| 7) THE PRODUCT APPROVALS FOR THE DOUBLE |
| OUTSWING ENTRY DOORS DO NOT MEET THE |
| WINDLOAD PRESSURES SPECIFIED IN THE |
| WINDLOAD SCHEDULE ON A1. |
| |
| 8) THE SITE SPECIFIC ENGINEERING DOES |
| NOT MEET THE REQUIRED PRESSURES FOR THE |
| FRENCH DOORS. |
| |
| 9) THE OVERHEAD GARAGE DOOR PRODUCT |
| APPROVAL DOES NOT MEET THE PRESSURES |
| LISTED ON THE WINDLOAD SCHEDULE ON A1. |
| |
| 10) THE SH 35 WINDOWS (W) AND (Y) WILL |
| REQUIRE 3/16" TEMPERED GLASS TO MEET THE |
| SPECIFIED WINDLOAD PRESSURES, BASED ON |
| THE PRODUCT APPROVAL THAT WAS SUBMITTED. |
| |
| 11) PLEASE REVIEW THE WINDLOAD PRESSURES |
| ON THE PLANS, THEY APPEAR TO BE HIGHER |
| THAN REQUIRED FOR EXPOSURE B. |
| |
| 12) THE KEY PLAN AND SCHEDULE FOR THE |
| STORM PANELS DO NOT MATCH THE PLANS. |
| PLEASE CORRECT. |
| |
| 13) THE PRODUCT APPROVALS FOR THE STORM |
| PANELS LIST THE MINIMUM PANEL LENGTH FOR |
| DIRECT MOUNT INSTALLATION AS 46". THE |
| SCHEDULE LISTS SMALLER LENGTHS. PLEASE |
| CORRECT. |
| |
| 14) THE CALK-IN ANCHORS ARE HI-LITED ON |
| THE PRODUCT APPROVAL FOR HOLLOW CONCRETE |
| BLOCK. ACCORDING TO THE PROD. APPROVAL |
| SCHEDULE, THEY CAN NOT BE USED FOR |
| HOLLOW BLOCK WITH C1 CONNECTION TYPE. |
| PLEASE CORRECT. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |