Plan Review Notes
Plan Review Notes For Permit 03072255
Permit Number 03072255
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-19 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.2.2.
  
 4) THE GLASS BLOCK IN THE MASTER BATH
 AND BATH 2 ARE IN HAZARDOUS LOCATIONS
 AND ARE REQUIRED TO BE TEMPERED OR HAVE
 A UNIFORM FACE THICKNESS OF 0.25 INCH
 PER FBC 2405.2.
  
 5) THE FULL BATH ON THE FIRST FLOOR IS
 REQUIRED TO HAVE A DOOR WITH A 29" CLEAR
 OPENING PER FBC 11-4.23.2.
  
 6) FBC 1609.4 NO LONGER ALLOWS A ONE-
 THIRD INCREASE IN THE STEEL CALCULATIONS
 FOR COMBINATION LOADS. PLEASE REVISE THE
 VALUES LISTED IN THE ANCHOR SCHEDULES ON
 SHEETS A7 AND A8 TO VALUES THAT DO NOT
 INCLUDE THIS INCREASE. SEE THE 2003 USP
 CATALOG.
  
 7) THE PRODUCT APPROVALS FOR THE DOUBLE
 OUTSWING ENTRY DOORS DO NOT MEET THE
 WINDLOAD PRESSURES SPECIFIED IN THE
 WINDLOAD SCHEDULE ON A1.
  
 8) THE SITE SPECIFIC ENGINEERING DOES
 NOT MEET THE REQUIRED PRESSURES FOR THE
 FRENCH DOORS.
  
 9) THE OVERHEAD GARAGE DOOR PRODUCT
 APPROVAL DOES NOT MEET THE PRESSURES
 LISTED ON THE WINDLOAD SCHEDULE ON A1.
  
 10) THE SH 35 WINDOWS (W) AND (Y) WILL
 REQUIRE 3/16" TEMPERED GLASS TO MEET THE
 SPECIFIED WINDLOAD PRESSURES, BASED ON
 THE PRODUCT APPROVAL THAT WAS SUBMITTED.
  
 11) PLEASE REVIEW THE WINDLOAD PRESSURES
 ON THE PLANS, THEY APPEAR TO BE HIGHER
 THAN REQUIRED FOR EXPOSURE B.
  
 12) THE KEY PLAN AND SCHEDULE FOR THE
 STORM PANELS DO NOT MATCH THE PLANS.
 PLEASE CORRECT.
  
 13) THE PRODUCT APPROVALS FOR THE STORM
 PANELS LIST THE MINIMUM PANEL LENGTH FOR
 DIRECT MOUNT INSTALLATION AS 46". THE
 SCHEDULE LISTS SMALLER LENGTHS. PLEASE
 CORRECT.
  
 14) THE CALK-IN ANCHORS ARE HI-LITED ON
 THE PRODUCT APPROVAL FOR HOLLOW CONCRETE
 BLOCK. ACCORDING TO THE PROD. APPROVAL
 SCHEDULE, THEY CAN NOT BE USED FOR
 HOLLOW BLOCK WITH C1 CONNECTION TYPE.
 PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714