Plan Review Notes
Plan Review Notes For Permit 03072132
Permit Number 03072132
Review Stop E
Sequence Number 1
Notes
Date Text
2003-08-04 00:00:00PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} DRYER VA IN THE LOAD CALCULATION MUST
 COMPLY WITH 210.18(5000 VA).
  
 3} THE AIR HANDLER IS SHOWN AS 10 KW ON
 THE SCHEDULE BUT CALCULATED @ 7400.IT
 WAS ALSO TAKEN AGAIN IN THE DEMAND FOR
 OTHER LOADS.PLEASE SEE 220.3(B).(100%).
  
 4} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} PLEASE INCLUIDE SMALL APPLIANCE
 CIRCUITS IN CALC.PER210.16(A).
  
 6} DINNING RM RECEPTACLE SPACING TO
 COMPLY WITH 210.52(A). SEE REVIEWD SET
 OF PLANS.
  
 7} GARAGE RECEPTACLES TO COMPLY WITH
 210.8(A)(2).GFI.
  
 8} ADD A SMOKE DETECTOR IN THE HALL
 OUTSIDE THE BEDROOMS PER 24.3.4
 NFPA-101.
  
 9} FIXTURES IN THE CLOSETS MUST COMPLY
 410.8
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718