Plan Review Notes For Permit 03072132 |
Permit Number |
03072132 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-08-04 00:00:00 | PLEASE PROVIDE THE FOLLOWING | | INFORMATION,MAKE NECESSARY CHANGES TO | | PLANS AND RESUBMIT FOR REVIEW. | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2} DRYER VA IN THE LOAD CALCULATION MUST | | COMPLY WITH 210.18(5000 VA). | | | | 3} THE AIR HANDLER IS SHOWN AS 10 KW ON | | THE SCHEDULE BUT CALCULATED @ 7400.IT | | WAS ALSO TAKEN AGAIN IN THE DEMAND FOR | | OTHER LOADS.PLEASE SEE 220.3(B).(100%). | | | | 4} PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S). PER 210-11-C-3 | | MUST BE 20A AND #12AWG. | | | | 5} PLEASE INCLUIDE SMALL APPLIANCE | | CIRCUITS IN CALC.PER210.16(A). | | | | 6} DINNING RM RECEPTACLE SPACING TO | | COMPLY WITH 210.52(A). SEE REVIEWD SET | | OF PLANS. | | | | 7} GARAGE RECEPTACLES TO COMPLY WITH | | 210.8(A)(2).GFI. | | | | 8} ADD A SMOKE DETECTOR IN THE HALL | | OUTSIDE THE BEDROOMS PER 24.3.4 | | NFPA-101. | | | | 9} FIXTURES IN THE CLOSETS MUST COMPLY | | 410.8 | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|