Plan Review Notes
Plan Review Notes For Permit 03071921
Permit Number 03071921
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-19 00:00:00*****CORRECTIONS******
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT PROTECTOIN REQUIRED FOR
 GLAZING; FBC1606.1.7.EITHER PROVIDE
 TWO COPIES OF A HURRICANE SHUTTER
 ATTACHMENT SCHEDULE AND PRODUCT
 APPROVALS, OR A SEPARATE PERMIT WILL BE
 REQUIRED.
  
 3.)DETAIL 38-A1, THE BOTTOM OF
 FOUNDATIONS SHALL EXTEND NO LESS THAN
 12" BELOW FINISH GRADE, FBC1804.1.3.
  
 4.)IS THE FRONT DOOR GLAZED?NO
 PRODUCT APPROVAL FOR THE DOOR WAS
 SUBMITTED.ONE METHOD OF EGRESS ON THE
 FIRST FLOOR MUST BE PROVIDED FBC1005.4.5
 2003 AMENDMENT.
  
 5.)DETAILS ON SHEET A6 HAVE ATTCHMENTS
 WHICH CONFLICT WITH THE USP CATALOG
 (EXAMPLE - 2,12,4).OTHERS MAY ALSO BE
 INCONSISTENT.CHECK ALL ATTACHMENTS.
  
 6.)SUBMIT PRODUCT APPROVALS FOR ALL
 GLAZING, DOORS, ROOF,MULLIONS,
 SHUTTERS.ANY PRODUCT APPROVALS NOT
 SUBMITTED BEFORE THE LAST REVIEW WILL
 REQUIRE SEPARATE PERMITS FOR THOSE
 ITEMS.
  
 7.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]