Plan Review Notes For Permit 03071919 |
Permit Number |
03071919 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-08-19 00:00:00 | ******CORRECTIONS******* | | | | 1.)THE WRONG SQUARE FOOTAGE IS ON THE | | IMPACT FEE STAMP. | | | | 2.)ADDITIONAL FEES, $17.83. | | | | 3.)PROVIDE A SOILS INVESTIGATION | | REPORT. | | | | 4.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS BEFORE A | | PERMIT CAN BE ISSUED. | | | | 5.)SHEET A5 SPECIFIES A SEMCO | | ATTACHMENT.THIS IS NOT AVAILABLE. | | | | 6.)NAILING FOR 4-A5 CONFLICTS WITH | | THE USP 2003 CATALOG.REVISE OR EXPLAIN | | HOW THIS DETAIL MEETS THE DESIGN | | REQUIREMENT OF 2550# UPLIFT.CHECK ALL | | OTHER ATTACHMENTS. | | | | 7.)IMPACT PROTECTION IS REQUIRED FOR | | GLAZING, FBC1606.1.7.EITHER PROVIDE | | TWO COPIES OF A HURRICANE SHUTTER | | ATTACHMENT SCHEDULE AND PRODUCT | | APPROVALS OR A SEPARATE PERMIT WILL BE | | REQUIRED. | | | | 8.)SUBMIT PRODUCT APPROVALS FOR ALL | | GLAZING, DOORS, ROOF, MULLIONS,SHUTTERS. | | ANY PRODUCT APPROVALS NOT SUBMITTED | | BEFORE THE LAST REVIEW WILL REQUIRE | | SEPARATE PERMITS FOR THOSE ITEMS. | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | [email protected] |
|