2003-07-31 00:00:00NOTE: PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATEDAND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 THERE APPEARS TO BE ADDED LOADS TO
 PANEL"DPGP",PLEASE SUPPLY A LOAD
 CALCULATION FOR THAT PANEL WITH
 EXISTING AND ADDED LOADS COMPUTED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  