Plan Review Notes For Permit 03071781 |
Permit Number |
03071781 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-08-18 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1-REVISE INSTALLATION SCHEDULE FOR | | STORM SHUTTERS. REVISE THE SPACING | | FOR WOOD ANCHORS. SEE THE ENGINEERED | | DRAWINGS FOR MAXIMUM SPACING ALLOWED. | | 2-RESUBMIT ENERGY CALCULATIONS WITH THE | | ENGINEER'S ORIGINAL SEAL, SIGNATURE | | AND DATE AS REQUIRED BY CHAPTER 471 | | OF FLORIDA STATUTES. | | 3-PROVIDE SOIL TEST REPORT WITH THE | | ENGINEER'S ORIGINAL SEAL, SIGNATURE | | AND DATE. CHAPTER 471 FLORIDA STATUTES |
|