2003-08-15 00:00:00 | DENIED |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) SUBMIT A FINAL SOIL TEST REPORT AS |
| REQUIRED BY THE PRELIMINARY SOIL REPORT |
| AND FBC 1804.2.2. |
| |
| 3) THE STRUCTURE IS LOCATED IN AN "AO" |
| FLOD ZONE AN ELEVATION CERTIFICATE WILL |
| BE REQUIRED. |
| |
| 4) REVISE NOTE #11 UNDER PLAN NOTES ON |
| C1. FBC 1606.1.4 REQUIRES PROTECTION OF |
| GLAZED OPENINGS IN WINDBOURNE DEBRIS |
| REGIONS AS WELL AS THE HVHZ. |
| |
| 5) REVISE NOTE #15 UNDER FRAMING NOTES |
| ON C1. ASTM C 1063 REQUIRES HIGH RIB |
| METAL LATH TO BE ATTACHED AT EACH RIB |
| (4"O.C.). |
| |
| 6) THE ENERGY CALCS. ARE REQUIRED TO BE |
| SIGNED BY THE OWNER/AGENT. SEE FBC |
| CHAPTER 13. |
| |
| 7) SPECIFY THE LENGTH/EMBED DEPTH OF THE |
| 1/2" DIA. A.B. FOR THE GARAGE DOOR BUCK |
| ON A4. |
| |
| 8) CLARIFY ON THE BUCK DETAIL FOR THE |
| SLIDING GLASS DOOR ON A4 THAT THE FRAME |
| IS FASTENED THROUGH THE 1X BUCK. SEE |
| FBC 1707.4.4.2. |
| |
| 9) DETAIL 6 ON A5 SPECIFIES A HANGER |
| WITH THROUGH BOLTS AT A BLOCK WALL. |
| PLEASE CLARIFY. |
| |
| 10) THE GLASS BLOCK OPENINGS IN THE |
| MASTER BATH ARE IN HAZARDOUS LOCATIONS |
| AND ARE REQUIRED TO BE TEMPERED OR HAVE |
| A MINIMUM UNIFORM FACE THICKNESS OF |
| 0.25" PER FBC 2405.2.2. PLEASE SPECIFY |
| ON THE PLANS. |
| |
| 11) THE BUILDING SET BACKS ON THE SITE |
| PLAN S-1 AND THE SURVEY DIFFER. PLEASE |
| CORRECT. |
| |
| 12) SUBMIT THE CLEAR OPENING DIMENSIONS |
| AND AREA FROM THE MANUFACTURER FOR THE |
| SH 24-4 EGRESS WINDOWS. |
| |
| 13) THE TAG FOR DETAIL 3 ON A5 IS SHOWN |
| ON THE FRAMING PLAN IN THE WRONG |
| LOCATION. |
| |
| 14) FBC 1609.4.3 DOES NOT ALLOW THE ONE- |
| THIRD INCREASE IN THE STEEL CALCULATIONS |
| FOR COMBINED LOADS. PLEASE REVISE THE |
| DETAILS ON A5 AND THE TRUSS CONNECTOR |
| SCHEDULE ON A6 TO VALUES THAT DO NOT |
| INCLUDE THIS INCREASE. SEE THE 2003 USP |
| CATALOG. |
| |
| 15) THE SITE SPECIFIC PRODUCT APPROVAL |
| LETTER FROM SCOTT DISHER DOES NOT |
| INDICATE THE LOT NUMBER. |
| |
| 16) THE SITE SPECIFIC ENGINEERING FOR |
| THE FIXED GLASS WINDOWS DOES NOT HAVE |
| THE 74"X 96" F.G.WINDOW AT THE LIVING |
| ROOM OR THE 18" DIAMETER F.G. WINDOW IN |
| BATH 2. |
| |
| 17) THE 37"X 24" FIXED GLASS WINDOW IN |
| THE FAMILY ROOM THAT IS IN THE END ZONE |
| EXCEEDS THE DESIGN PRESSURES LISTED IN |
| THE SITE SPECIFIC ENGINEERING. |
| |
| 18) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - SINGLE HUNG WINDOWS |
| - STRUCTURAL MULLIONS (CONNECTING THE |
| (2) 35SH WINDOWS AT THE MASTER SUITE) |
| |
| 19) THE FRONT ELEVATION LISTS THE WRONG |
| SIZE M.O. FOR THE WINDOW IN BEDROOM 4. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |