Plan Review Notes
Plan Review Notes For Permit 03071439
Permit Number 03071439
Review Stop E
Sequence Number 4
Notes
Date Text
2004-09-01 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE RISER SHOWS PANEL
 "C" AS 100A, YET PANEL SCHEDULE AND
 PLANS/LOAD CALCS SHOW 125A??
  
 2)NOTE: PLEASE SEE PANEL SCHEDULES SHOW
 A TOTAL OF 9 AHU'S AND YET LOAD CALCS
 INDICATE 8 UNITS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  