Date |
Text |
2003-10-08 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FHA-98 DESIGN MANUAL |
| |
| A) THE FOLLOWING COMMENTS WERE NOT ADD- |
| RESSED FROM THE FIRST REVEIW. THE COMM- |
| ENT NUMBERS SHALL STAY THE SAME FOR |
| CLAIRITY. |
| 3) SHT P01 OF 29 FLOOR PLAN FOR A101/S3 |
| SECOND FLOOR STACK NOT SHOWN ON PLUMBING |
| LAYOUT. |
| 7) A.SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| C. TYPE OF GAS, (LP OR NATURAL) |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34). - GAS CHART SHOWS 80,000 BTU'S |
| FOR NORTH ADDITION, BUT FLOOR PLAN SHOWS |
| 105,000 BTU'S. PLEASE CLAIRFY. |
| F. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| GAS CODE SECTION 304. |
| G. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| SHOWS .75 PSI. VERIFY WITH GAS PROVIDER. |
| NORMAL PRESSURE IS EITHER .50 PSI OR |
| 2 PSI. PLEASE CLAIRFY. |
| H. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2001 FUEL GAS CODE |
| SECS. 502 THRU 506. |
| I. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| J. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| NEW COMMENT FOR GAS: |
| K. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2 |
| 10) SHT A04 OF 29 UNITS A101, A102, AND |
| A103 SHALL COMPLY WITH FHA-98 AMENDED |
| DESIGN MANUAL, REQUIREMENTS 1 THRU 7. |
| DETAILS SHALL BE SUBMITTED. SHOW ALL |
| BACKING PER REQ #6. SPECIFICATION "A" OR |
| "B" BATHROOMS PER REQ. #7B, SHOW CLEAR |
| FLOOR SPACE FOR ALL BATHROOM FIXTURES & |
| KITCHEN FIXTURES. SHOW OPENING SIZE FOR |
| ALL TOILETS, HEIGHTS FOR LAVS. ECT. |
| |
| REVIEW BY KEN STEVENS |