2003-10-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
  
 A) THE FOLLOWING COMMENTS WERE NOT ADD-
 RESSED FROM THE FIRST REVEIW. THE COMM-
 ENT NUMBERS SHALL STAY THE SAME FOR
 CLAIRITY.
 3) SHT P01 OF 29 FLOOR PLAN FOR A101/S3
 SECOND FLOOR STACK NOT SHOWN ON PLUMBING
 LAYOUT.
 7) A.SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). - GAS CHART SHOWS 80,000 BTU'S
 FOR NORTH ADDITION, BUT FLOOR PLAN SHOWS
 105,000 BTU'S. PLEASE CLAIRFY.
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 SHOWS .75 PSI. VERIFY WITH GAS PROVIDER.
 NORMAL PRESSURE IS EITHER .50 PSI OR
 2 PSI. PLEASE CLAIRFY.
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 NEW COMMENT FOR GAS:
 K. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 10) SHT A04 OF 29 UNITS A101, A102, AND
 A103 SHALL COMPLY WITH FHA-98 AMENDED
 DESIGN MANUAL, REQUIREMENTS 1 THRU 7.
 DETAILS SHALL BE SUBMITTED. SHOW ALL
 BACKING PER REQ #6. SPECIFICATION "A" OR
 "B" BATHROOMS PER REQ. #7B, SHOW CLEAR
 FLOOR SPACE FOR ALL BATHROOM FIXTURES &
 KITCHEN FIXTURES. SHOW OPENING SIZE FOR
 ALL TOILETS, HEIGHTS FOR LAVS. ECT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]