2003-10-01 00:00:00 | PROVISO: | | 1.PLAN SHEET M01 NOTE #17, AUXILIARY | | DRAIN PAN SHALL HAVE FLOAT SWITCH OR | | SECONDARY DRAIN TERMINATING AT A | | CONSPICUOUS POINT TO SERVE AS AN ALARM | | THAT THE PRIMARY DRAIN IS RESTRICTED. | | | | 2.AHU IN THE ATTIC OR CEILING SPACE | | SHALL COMPLY WITH 2001 FBC CHAPTER 13 | | SECTION 610.1.ABC.3.5.2.ACCESS SHALL | | COMPLY WITH 306.3 OF THE 2001 FBC(M). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|