Plan Review Notes
Plan Review Notes For Permit 03071439
Permit Number 03071439
Review Stop E
Sequence Number 2
Notes
Date Text
2003-09-24 00:00:00*************** UNSAT ***************
  
 PLEASE SEE THAT MANY COMMENTS FROM
 FIRST REVIEW NEED TO BE ADDRESSED FULLY.
  
  
 1)NOTE: PLEASE SEE SERVICE, PLEASE
 CORRELATE PANELS/RISER/ LOAD CALCULATION
 -S VOLTAGES ETC.
 LOAD CALCS SHOW 120/208V AND SOME PANELS
 SHOW 120/240V PLEASE VERIFY VOLTAGE AND
 SUBMIT ALL LOAD CALCS/PANEL TO MATCH.
 PLEASE CORRELATE RISER.
 PLEASE SEE THAT ALL PANELS, INCLUDING
 150A/125A ETC ARE SHOWN AS 42 CIRCUIT
 PANELS. PLEASE NOTE, A 125A PANEL IS NOT
 MADE FOR 42 CIRCUITS ETC.
 PLEASE SEE THAT PANEL 'A' IS SHOWN
 FEEDING PANELS B AND C, YET RISER DOES
 NOT SHOW THIS?
 ETC ETC.
  
 2)NOTE: PLEASE SEE 250.50 FOR GROUNDING.
 RISER NOTES, GROUND TO FOOTER STEEL OR
 COLD WATER OR GAS. PLEASE SEE THAT ALL
 OF THESE ARE REQ'D.
  
 3)NOTE: PLEASE SEE COMMENT ABOUT SD`S
 ON FIRST REVIEW. THIS COMMENT WAS MEANT
 FOR MAIN HOUSE. PLEASE SEE THAT SD'S ARE
 NOW PLACED OUTSIDE FOR SLEEPING ROOMS
 ON DETACHED BLDG??? NOT TO BE INSTALLED.
 MISSING FOR INSIDE.
  
 4)NOTE: PLEASE SHOW LOAD CALCUALTIONS
 FOR ENTIRE SERVICE PER 220. PLEASE SEE
 LOAD CALCS FOR AHU'S ETC ETC.
  
 5)NOTE: PLEASE SEETHAT AN EXT CIRCUIT
 IS SHOWN FOR MAIN HOUSE AND ONLY ONE
 EXT SIGN SEEMS TO BE SHOWN? PLEASE SEE
 FIRE REVIEW COMMENT AND ALSO SEE 700.12E
 FOR CIRCUITING.
  
 6)NOTE: PLEASE SEE THAT WATER HEATER(S)
 STILL SHOWN ON ELECTRICAL PANEL? ALSO
 SHOWN AS GAS?
  
 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT. MAINS/PANELS/ BREAKER
 S ARE ALL TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT. 110.9/215.5
  
 8)NOTE: PLEASE CORREALET MECH/PLUMB/GAS
 PLAN WITH ELECTRICAL. SHOWS DRYER ALSO
 BEING GAS AND YET ON ELECTRICAL, THIS
 IS SHOWN AS ELEC??
  
 9)NOTE: PLEASE SEE THAT AHU'S ARE NOW
 SHOWN IN ATTIC SPACE, PLEASE SHOW LIGHT
 AND RECEPT REQ'D UNDER 210.63/210.70
  
 10)NOTE: PLEASE INDICATE INDIVIDUAL KW
 LOADS FOR AHU'S.
  
 11)NOTE: PLEASE SEE FBC CHAPTER 34
 3401.7.2/3401.7.1
 104.1 CHANGE OF OCCUPANCY TEC.
 PLEASE SHOW EXISTING ELECTRIC AND KNOW
 THAT ALL EXISTING MUST BE BROUGHT UP TO
 CODE.
  
 12)NOTE:PLEASE SEE COPY OF FS. 553.80(2)
 -(B) WITH RESPECT TO DESIGN PROFESSIONAL
 -S FOR PLAN REVIEWS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]