2003-09-24 00:00:00 | *************** UNSAT *************** |
| |
| PLEASE SEE THAT MANY COMMENTS FROM |
| FIRST REVIEW NEED TO BE ADDRESSED FULLY. |
| |
| |
| 1)NOTE: PLEASE SEE SERVICE, PLEASE |
| CORRELATE PANELS/RISER/ LOAD CALCULATION |
| -S VOLTAGES ETC. |
| LOAD CALCS SHOW 120/208V AND SOME PANELS |
| SHOW 120/240V PLEASE VERIFY VOLTAGE AND |
| SUBMIT ALL LOAD CALCS/PANEL TO MATCH. |
| PLEASE CORRELATE RISER. |
| PLEASE SEE THAT ALL PANELS, INCLUDING |
| 150A/125A ETC ARE SHOWN AS 42 CIRCUIT |
| PANELS. PLEASE NOTE, A 125A PANEL IS NOT |
| MADE FOR 42 CIRCUITS ETC. |
| PLEASE SEE THAT PANEL 'A' IS SHOWN |
| FEEDING PANELS B AND C, YET RISER DOES |
| NOT SHOW THIS? |
| ETC ETC. |
| |
| 2)NOTE: PLEASE SEE 250.50 FOR GROUNDING. |
| RISER NOTES, GROUND TO FOOTER STEEL OR |
| COLD WATER OR GAS. PLEASE SEE THAT ALL |
| OF THESE ARE REQ'D. |
| |
| 3)NOTE: PLEASE SEE COMMENT ABOUT SD`S |
| ON FIRST REVIEW. THIS COMMENT WAS MEANT |
| FOR MAIN HOUSE. PLEASE SEE THAT SD'S ARE |
| NOW PLACED OUTSIDE FOR SLEEPING ROOMS |
| ON DETACHED BLDG??? NOT TO BE INSTALLED. |
| MISSING FOR INSIDE. |
| |
| 4)NOTE: PLEASE SHOW LOAD CALCUALTIONS |
| FOR ENTIRE SERVICE PER 220. PLEASE SEE |
| LOAD CALCS FOR AHU'S ETC ETC. |
| |
| 5)NOTE: PLEASE SEETHAT AN EXT CIRCUIT |
| IS SHOWN FOR MAIN HOUSE AND ONLY ONE |
| EXT SIGN SEEMS TO BE SHOWN? PLEASE SEE |
| FIRE REVIEW COMMENT AND ALSO SEE 700.12E |
| FOR CIRCUITING. |
| |
| 6)NOTE: PLEASE SEE THAT WATER HEATER(S) |
| STILL SHOWN ON ELECTRICAL PANEL? ALSO |
| SHOWN AS GAS? |
| |
| 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT. MAINS/PANELS/ BREAKER |
| S ARE ALL TO BE RATED FOR THE AVAILABLE |
| FAULT CURRENT. 110.9/215.5 |
| |
| 8)NOTE: PLEASE CORREALET MECH/PLUMB/GAS |
| PLAN WITH ELECTRICAL. SHOWS DRYER ALSO |
| BEING GAS AND YET ON ELECTRICAL, THIS |
| IS SHOWN AS ELEC?? |
| |
| 9)NOTE: PLEASE SEE THAT AHU'S ARE NOW |
| SHOWN IN ATTIC SPACE, PLEASE SHOW LIGHT |
| AND RECEPT REQ'D UNDER 210.63/210.70 |
| |
| 10)NOTE: PLEASE INDICATE INDIVIDUAL KW |
| LOADS FOR AHU'S. |
| |
| 11)NOTE: PLEASE SEE FBC CHAPTER 34 |
| 3401.7.2/3401.7.1 |
| 104.1 CHANGE OF OCCUPANCY TEC. |
| PLEASE SHOW EXISTING ELECTRIC AND KNOW |
| THAT ALL EXISTING MUST BE BROUGHT UP TO |
| CODE. |
| |
| 12)NOTE:PLEASE SEE COPY OF FS. 553.80(2) |
| -(B) WITH RESPECT TO DESIGN PROFESSIONAL |
| -S FOR PLAN REVIEWS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |