2003-08-18 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 11 |
| FHA-98 DESIGN MANUAL |
| |
| 1) SHTS A05/07/09 SUBMIT CALCULATIOS FOR |
| PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| SQUARE FOOTAGE OF ROOF & SHOW 1/2 AREA |
| OF VERTICAL WALLS (PARAPETS) IN CALCUL- |
| ATIONS. SHOW SIZE OF ALL DOWNSPOUTS. |
| SHOW LOCATIONS FOR ALL SECONDARY ROOF |
| DRAINS (SCUPPERS) - PROVIDE A DETAIL FOR |
| ALL DRAINS. SHOW HEIGHT & WIDTH. |
| 2) SHT P01 OF 29 - S/4 & S/5, SHOW ALL |
| PIPE SIZES ON ISOMETRIC DIAGRAMS. STAND- |
| PIPE REQUIRED FOR WASH MACHINE. SECTION |
| 802.4. - CLEANOUTS REQUIRED 4' ABOVE |
| FLOOR AT WASH MACHINE. SECTION 708.10 |
| 3) SHT P01 OF 29 FLOOR PLAN FOR A101/S3 |
| SECOND FLOOR STACK NOT SHOWN. |
| 4) SHT P01 OF 29 FLOOR PLAN FOR A102/S4 |
| SHOWS PIPE RUNNING WEST OF SHOWER AT 2" |
| THEN 1-1/2" AND TERMINATES IN LAUNDRY |
| ROOM BY UNIT A103. PLEASE CLAIRFY. ALSO |
| FLOOR PLAN DOES NOT SHOW WHERE IT TIES |
| INTO SEWER. |
| 5) SHT P02 BY 29 ISOMETRIC RISER S/3 |
| 2ND FLOOR BATHROOM SHALL TIE IN DOWN- |
| STREAM OF 1ST FLOOR W/C. |
| 6) SHT P02 OF 29 ISOMETRIC RISER DOES |
| NOT REFLECT FLOOR PLAN. SEE COMMENT #4. |
| 7) GAS PERMIT APPLICATION REQUIREMENTS. |
| SEPARATE GAS PERMIT REQUIRED. |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| (GAS NOTES STATES POLYETHYLENE PIPE TO |
| BE USED ABOVE GROUND. NOT APPROVED PER |
| SECTION 403.3. DELETE REFERENCE). |
| C. TYPE OF GAS, (LP OR NATURAL) |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34). |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). |
| F. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| GAS CODE SECTION 304. |
| G. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| H. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2001 FUEL GAS CODE |
| SECS. 502 THRU 506. |
| (IF LP GAS FOLLOWING INFO REQUIRED) |
| I. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| J. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| 8) SHT P02 OF 29 PLUMBING NOTES #8, |
| TABLE 704.1 - PIPE SIZE 2-1/2" OR LESS |
| SHALL BE RUN AT 1/4" PER FOOT SLOPE MIN. |
| 9) SHT P02 OF 29 PLUMBING NOTES #29. |
| AIR CHAMBERS ARE NOT APPROVED. DELETE |
| FROM REFERENCE. |
| 10) SHT A04 OF 29 UNITS A101 & A102 |
| SHALL COMPLY WITH FHA-98 AMENDED DESIGN |
| MANUAL, REQUIREMENTS 1 THRU 7. DETAILS |
| SHALL BE SUBMITTED. SHOW ALL BACKING PER |
| REQ #6. SPECIFICATION "A" OR "B" BATH- |
| ROOMS PER REQ. #7B, SHOW CLEAR FLOOR |
| SPACE FOR ALL BATHROOM FIXTURES. SHOW |
| OPENINGS FOR TOILETS, HEIGHT FOR LAVS. |
| ECT. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |