Plan Review Notes For Permit 03071439 |
Permit Number |
03071439 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-08-20 00:00:00 | DENIED: | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | FOR REVIEW: | | | | 1. PLAN SHEET M01, INDICATES DUCT | | PENTRATIONS THROUGH WALLS WITH FIRE | | RESISTANCE RATING OF 1 TO 2 HR.AS PER | | 2001 FBC(M) 607.1.2. | | | | 2. CONDENSATE SHALL TERMINATE A MINIMUM | | OF 12" AWAY FROM THE BUILDING STRUCTURE | | AS PER 2001 FBC 1503.4.4. | | | | 3. PLEASE PROVIDE MANUFACTURER SUBMITTAL | | DATA ON THE FIRE PLACE. | | | | 4. PROVIDE CALCULATIONS FOR COMBUSTUTION | | AIR (CONFINED SPACE). 2001 FBC(M) | | DEFINITIONS, CONFINED SPACE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|