2003-08-20 00:00:00DENIED:
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1. PLAN SHEET M01, INDICATES DUCT
 PENTRATIONS THROUGH WALLS WITH FIRE
 RESISTANCE RATING OF 1 TO 2 HR.AS PER
 2001 FBC(M) 607.1.2.
  
 2. CONDENSATE SHALL TERMINATE A MINIMUM
 OF 12" AWAY FROM THE BUILDING STRUCTURE
 AS PER 2001 FBC 1503.4.4.
  
 3. PLEASE PROVIDE MANUFACTURER SUBMITTAL
 DATA ON THE FIRE PLACE.
  
 4. PROVIDE CALCULATIONS FOR COMBUSTUTION
 AIR (CONFINED SPACE). 2001 FBC(M)
 DEFINITIONS, CONFINED SPACE.
  