Plan Review Notes
Plan Review Notes For Permit 03071439
Permit Number 03071439
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-08-20 00:00:001) PLEASE CLEARLY IDENTIFY ALL SMOKE
 DETECTOR LOCATIONS. THE ELECTRICAL
 LEGEND DOES NOT CORRESPOND WITH
 REGARDS TO SMOKE DETECTORS.
  
 2) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 3) STORAGE NOTED UNDER STAIR SECTION AT
 NORTH ELEVATION. STORAGE IS ALLOWED
 UNDERNEATH THE STAIR SHALL BE THE
 SAME RATING AS THE STAIR.
  
 4) NO WINDOWS ARE ALLOWED WITHIN TEN
 FEET OF ANY EXIT STAIRS. PLEASE SEE
 NOTES WRITTEN BY HISTORIC DEPT.
  
 5) ALL NEW STAIRS SHALL HAVE HANDRAILS
 ON BOTH SIDES.
  
 6) TREAD SIZES DO NOT APPEAR TO BE
 CORRECT 11 INCH TREADS ARE ALLOWED
 NOT 10.86.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL