2003-07-30 00:00:00 | *********** UNSAT ******************* |
| |
| PLEASE SEE THAT PLANS ARE NOT COMPLETE |
| FOR FULL REVIEW. |
| |
| 1)NOTE: PLEASE SHOW LOCATION FOR ALL |
| SERVICE PANELS AND DISCONNECTS. |
| PLEASE SHOW LOCATION OF MAIN SERVICE. |
| |
| 2)NOTE: PLEASE SEE RISER, SHOWS 400A |
| MAIN FEEDING TWO SEPARATE PANELS, ONE |
| 200A, ONE 150A? PLEASE SUBMIT PANEL |
| SCHEDULE FOR 400A MAIN IF THIS A MDP? |
| 215.5/110.9 |
| PLEASE ALSO SUBMIT AIC RATING FOR 400A |
| MAIN. |
| |
| 3)NOTE: PLEASE SEE MISSING PANELS AT |
| 2-STORY APTS? PLEASE SEE 225.31 FOR |
| MEANS OF DISCONNECT AT DETACHED STRUCT- |
| -URES. |
| |
| 4)NOTE: PLEASE SUBMIT GROUNDING FOR |
| ALL DEATCHED BLDGS PER 250-32. |
| |
| 5)NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTORS PER 250.110 AND |
| SIZE PER 250.122FOR ALL SUB-PANELS |
| AFTER FIRST MEANS OF DISC. 250.24 |
| |
| 6)NOTE: PLEASE LIST ALL REQ`D ARC FAULT |
| PROTECTED CIRCUITS ON PANEL SCHEDULE(S) |
| PER 210.12 |
| |
| 7)NOTE: PLEASE ALSO SHOW ALL A/C UNITS |
| AND DISC'S PER 440.11 |
| RECEPTS NOW REQ'D FOR COND UNITS PER |
| 210.63 UNDER NEW 2002 NEC. |
| |
| 8)NOTE: PLEASE CORRELATE RISER AND PANEL |
| -BOARD "A", SHOWN AS 200A ON RISER AND |
| AS 400A ON SCHEDULE? |
| |
| 9)NOTE: PLEASE SEE RISER, SHOWS ONE |
| POOL PUMP, YET PANEL 'A' SHOWS 1-20A |
| BRKR FOR ONE, PANEL 'B' SHOWS ANOTHER |
| POOL PUMP W/ 2P-30A AND LOAD CALCS FOR |
| PANEL 'B' SHOWS @ 1.5 KW?? PLEASE |
| CORRELATE. |
| |
| 10)NOTE: PLEASE SEE MISSING SD`S. TO BE |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS |
| NFPA-72 8-1.4.2 AND FBC |
| |
| 11)NOTE: PLEASE LIST THE REQ'D SMALL |
| APPLIANCE CIRCUITS MISSING . 210.52/ |
| 210.11C.1, 220.16 |
| |
| 12)NOTE: PLEASELIST THE REQ'D DEDICAT- |
| -ED BATH CIRCUIT(S) 210.52D/ 210.11C.3 |
| |
| 13)NOTE: PLEASE SEE FBC CHAPTER 34, |
| 3401.7.2, 3401.7.1 SEEFBC AND |
| CITY-WIDE ADMIN CODE. 104.1 FOR |
| CHANGE IN OCCUPANCY. |
| PLEASE SHOW ALL EXISTING ELECTRICAL AS |
| "E", PLEASE SHOW AS BRINGING UP TO CODE |
| FOR ELECTRICAL. |
| |
| 14)NOTE: PLEASE CORRELATE ALLAHU LOADS |
| , OCP, AWG. SHOWN AS 20A AND LOAD CALCS |
| WAY EXCEED THESE. PLEASE SHOW LOADS FOR |
| ALL AHU HEAT STRIPS. |
| 240/424.3B |
| |
| 15)NOTE: PLEASE SEE MIN CIRCUIT FOR |
| WASHER 20A/#12, SHOWN AS #14 |
| |
| 16)NOTE: PLEASE SEE GARAGE RECEPTS TO |
| BE SHOWN AS GFI/GFI PROTECTED. 210.8 |
| |
| 17)NOTE: PLEASE CORRELATE PLANS, SHOWS |
| GAS WATER HEATERS AND ELECTRICAL? |
| |
| PLEASE NOTE, DUE TO MANY CHANGES IN PLAN |
| -S TO MEET NEC CODE COMPLIANCE, THERE |
| MAY BE OTHER COMMENTS TO FOLLOW. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. PLEASE ALSO GO OVER ENTIRE SET |
| OF PLANS. |
| IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| |
| |