2003-07-30 00:00:00*********** UNSAT *******************
  
 PLEASE SEE THAT PLANS ARE NOT COMPLETE
 FOR FULL REVIEW.
  
 1)NOTE: PLEASE SHOW LOCATION FOR ALL
 SERVICE PANELS AND DISCONNECTS.
 PLEASE SHOW LOCATION OF MAIN SERVICE.
  
 2)NOTE: PLEASE SEE RISER, SHOWS 400A
 MAIN FEEDING TWO SEPARATE PANELS, ONE
 200A, ONE 150A? PLEASE SUBMIT PANEL
 SCHEDULE FOR 400A MAIN IF THIS A MDP?
 215.5/110.9
 PLEASE ALSO SUBMIT AIC RATING FOR 400A
 MAIN.
  
 3)NOTE: PLEASE SEE MISSING PANELS AT
 2-STORY APTS? PLEASE SEE 225.31 FOR
 MEANS OF DISCONNECT AT DETACHED STRUCT-
 -URES.
  
 4)NOTE: PLEASE SUBMIT GROUNDING FOR
 ALL DEATCHED BLDGS PER 250-32.
  
 5)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS PER 250.110 AND
 SIZE PER 250.122FOR ALL SUB-PANELS
 AFTER FIRST MEANS OF DISC. 250.24
  
 6)NOTE: PLEASE LIST ALL REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE(S)
 PER 210.12
  
 7)NOTE: PLEASE ALSO SHOW ALL A/C UNITS
 AND DISC'S PER 440.11
 RECEPTS NOW REQ'D FOR COND UNITS PER
 210.63 UNDER NEW 2002 NEC.
  
 8)NOTE: PLEASE CORRELATE RISER AND PANEL
 -BOARD "A", SHOWN AS 200A ON RISER AND
 AS 400A ON SCHEDULE?
  
 9)NOTE: PLEASE SEE RISER, SHOWS ONE
 POOL PUMP, YET PANEL 'A' SHOWS 1-20A
 BRKR FOR ONE, PANEL 'B' SHOWS ANOTHER
 POOL PUMP W/ 2P-30A AND LOAD CALCS FOR
 PANEL 'B' SHOWS @ 1.5 KW?? PLEASE
 CORRELATE.
  
 10)NOTE: PLEASE SEE MISSING SD`S. TO BE
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS
 NFPA-72 8-1.4.2 AND FBC
  
 11)NOTE: PLEASE LIST THE REQ'D SMALL
 APPLIANCE CIRCUITS MISSING . 210.52/
 210.11C.1, 220.16
  
 12)NOTE: PLEASELIST THE REQ'D DEDICAT-
 -ED BATH CIRCUIT(S) 210.52D/ 210.11C.3
  
 13)NOTE: PLEASE SEE FBC CHAPTER 34,
 3401.7.2, 3401.7.1 SEEFBC AND
 CITY-WIDE ADMIN CODE. 104.1 FOR
 CHANGE IN OCCUPANCY.
 PLEASE SHOW ALL EXISTING ELECTRICAL AS
 "E", PLEASE SHOW AS BRINGING UP TO CODE
 FOR ELECTRICAL.
  
 14)NOTE: PLEASE CORRELATE ALLAHU LOADS
 , OCP, AWG. SHOWN AS 20A AND LOAD CALCS
 WAY EXCEED THESE. PLEASE SHOW LOADS FOR
 ALL AHU HEAT STRIPS.
 240/424.3B
  
 15)NOTE: PLEASE SEE MIN CIRCUIT FOR
 WASHER 20A/#12, SHOWN AS #14
  
 16)NOTE: PLEASE SEE GARAGE RECEPTS TO
 BE SHOWN AS GFI/GFI PROTECTED. 210.8
  
 17)NOTE: PLEASE CORRELATE PLANS, SHOWS
 GAS WATER HEATERS AND ELECTRICAL?
  
 PLEASE NOTE, DUE TO MANY CHANGES IN PLAN
 -S TO MEET NEC CODE COMPLIANCE, THERE
 MAY BE OTHER COMMENTS TO FOLLOW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE ALSO GO OVER ENTIRE SET
 OF PLANS.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW