2003-08-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03071439
 ADD: 1608 LAKE AVE
 CONT: PAUL NEWMAN
 TEL: (561)719-4248
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ASSUMPTIONS: EXISTING RESIDENCE IS TO BE
 USED AS A SINGLE FAMILY RESIDENCE.
  
 ACTION: DENIED
  
 1) PROVIDE 2 CURRENT COPIES OF SIGNED &
 SEALED SURVEYS WITH PROPOSED IMPROVEMENT
 TO BE COMPLETED.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 SURVEY'S ARE NOT SEALED.
  
 2) THE OUTDOOR POOL SHALL COMPLY WITH
 SECTION 424.2.17.1 THROUGH 424.2.17.1.15
  
 3)BED & BREAKFAST BEING A R-3 CLASSIFICA
 TION ( ROOMING HOUSE) BY DEFINITION
 MEETS THE REQUIREMENTS FOR SECTION 425,
 PUBLIC LODGING ESTABLISHMENTS
 425.3.4.1 SPECIALIZED SMOKE DETECTORS,
 FOR THE DEAF AND HEARING-IMPAIRED SHALL
 BE MADE AVAILABLE UPON REQUEST BY GUESTS
 IN TRANSIENT PUBLIC LODGING ESTABLISH-
 MENTS.
  
 4) MEASUREMENTS OF MEANS OF EGRESS,
 DOORWAYS 1003.2.3.1 THE CLEAR OPENING AT
 SWING DOORS SHALL BE MEASURED BETWEEN
 THE FACE OF THE DOOR AND THE STOP, WITH
 THE DOOR AND THE STOP, WITH THE DOOR
 OPEN 90 DEGREES.
 TABLE 1004 HEADING: MINIMUM CLEAR OPEN-
 ING OF EXIT DOORS FOR R-3 32".
 SEE THE FRENCH ENTRY DOORS LISTED AS
 DOOR# 10 AS (2) 2'-6" DOORS. CLEAR OPEN-
 ING WOULD BE APPROX. 28".
  
 5) CONTRACTOR HAS SUBMITTED IMPACT AND
 NON IMPACT PRODUCT APPROVAL FOR WINDOWS
 AND DOORS. PLEASE PROVIDE A KEY PLAN
 WHICH IDENTIFIES ALL OPENINGS AND A
 LIST OF WHICH OPENINGS ARE TO BE IMPACT
 RATED AND WHICH AREN'T. THIS WILL ALSO
 TIE TO THE STORM SHUTTER REQUIREMENTS
 LISTED BELOW:
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE. SAMPLE ATTACHED.
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) CASEMENT WINDOWS
 B) MULLIONS
 C) FRENCH DOORS W/ SIDE LIGHTS
 D) GARAGE OVERHEAD DOORS
  
 7)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 8)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 9)DISCREPANCY BETWEEN A-03 / A-12 AND
 WINDOW SCHEDULE, THE BATH WINDOW "D",
 A SECOND ISSUE IS THE WINDOW"C" ELEVA-
 TIONS VS THE WINDOW SCHEDULE.
  
 10) SHEET A-03 INDICATES THE USE OF
 VANGUARD PRE-FAB FIREPLACE:
 2806.1.2 FACTORY BUILT FIREPLACES
 SHALL BE TESTED IN ACCORDANCE WITH AND
 MEET THE REQUIREMENTS OF UL 127.
 CHIMNEYS FOR THE USE WITH FACTORY-
 BUILT FIREPLACES SHALL MEET THE
 REQUIREMENTS OF UL 127.
 2810 FRESH AIR INTAKES, FRESH AIR
 INTAKESSHALL BE SCREENED WITH A CORRO-
 SION RESITANT MATERIAL NOT LARGER THAN
 1/2 INCH MESH. FRESH AIR INTAKES SHALL
 NOT BE TAKEN FROM A LOCATION CLOSER THAN
 10 FT FROM ANY CHIMNEY OR VENT OUTLET OR
 SANITARY SEWER VENT OUTLET, UNLESS SUCH
 VENT IS NOT LESS THAN 24" ABOVE THE
 FRESH AIR VENT. FRESH AIR INTAKE VENTS
 LOCATED ON THE ROOFS WILL BE PROPERLY
 MARKED WITH A UNIVERSAL MARKING,
 ***"INTAKE"***, PERMANETLY ATTACHED.
 SEE 705.1.1.4 FOR FIRE PROTECTION.
  
 11) ADDITIONAL INFORMATION REQUIED:
 VARIOUS DETAIL SHEETS INDICATETHE USE
 OF (2) 2X10 LEDGERS BUT NO DEPTH DIMEN-
 SION IS PROIDED FOR ANY FASTENER.
  
 12) SHEET A06/A-08 ROOF FRAMING PLANS
 DO NOT PROVIDE UPLIFT INFORMATION.
 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD CARRY-
 ING CAPACITY.
 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
 PROVIDE A TRUSS ANCHOR SCHEDULE!
 1606.2.4. MAIN WIND FORCE RESISTING
 SYSTEM,SHALL BE DESIGNED FOR VERTICAL
 AND HORIZONTAL LOADS BASED ON THE COM-
 BINED LEEWARD AND WINDWARD PRESSURES
 FOR WALLS AND ROOFS.
 SHEET A-14 NOTE FOR SIMPSON ANCHOR
 ETA-14, NOT IN THE CURRENT 2003 HIGH
 WIND CATALOG. PROVIDE NEW ANCHOR.
  
 13)1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 14) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 15)1015.2 HEIGHT. GUARDRAILS SHALL
 FORM A VERTICAL PROTECTIVE BARRIER NOT
 LESS THAN 42" HIGH.
 1015.3 OPENINGS. OPEN GUARDRAILS
 SHALL HAVE INTERMEDIATE RAILS OR ORNA-
 MENTAL PATTERNS SUCH AS A 4" DIAMETER
 SPHERE CAN NOT PASS THROUGH. A BOTTOM
 RAIL OR CURB SHALL BE PROVIDED THAT WILL
 REJECT THE PASSAGE OF 2" DIAMETER
 SPHERE.
  
 16)1608.2.3 THE GUARDRAIL SYSTEM SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST A
 200 LB CONCENTRATED HORIZONTAL LOAD
 APPLIED ON A 1 SQ FT AREA AT ANY POINT
 IN THE SYSTEM INCLUDING INTERMEDIATE
 RAILS OR OTHER ELEMENTS SERVING THIS
 PURPOSE.
  
 17) SHEET A-16 STAIRS, NOTE NOT CLEAR
 #5'S @6" IS THIS FOR TOP AND BOTTOM
 REBAR TO BE AT 6" O. C.
  
 18) SAME DETAIL WHAT TYPE OF FINISH
 MATERIALS IS THE BALCONY MADE OF?
  
 19) ADDITIONAL INFORMATION: A-14/A-15
 BOTH ARE INDICATED TO HAVE A RAISED
 PLANTER, PROVIDE THE LOAD CALCULATION
 PROVIDE INFO FOR THE HANGERS, IS THE
 DECK BEING 3/8 " A TYPO?
  
 20) PROVIDE CAST-CRETE LINTEL SHEETS.
  
 21)*******BUILDING OFFICIAL HAS DETER-
 MINED THAT THIS WILL NOT BE A R-3 RESI-
 DENCE BED & BREAKFAST BUT A R-1 BOARDING
 HOUSE WITH 6 UNITS. THE ADDITION TO THE
 EXISTING RESIDENCE WILL BE CONSIDERED A
 SEPERATE 6TH GUEST ROOM. THE PLANS INDI-
 CATE A 1-HR WALL SEPERATING THE TENANT
 SPACE FROM THE COMMON LIVING QUARTERS.
  
 22) SINCE THE REVIEW IS NOW A R-1 BOARD-
 ING HOUSE FL ACCESSIBILITY NOW BECOMES A
 ISSUE. AN ACCESSIBLE ROUTE TO ALL COMMON
 AREAS,RAMPS, NOT STEPS, VERTICAL ACCESSI
 BILITY TO NOT ONLY THE OFFICE, DINING
 ROOM, BOTH LAUNDRY AREAS, THE SECOND
 FLOOR UNITS AND ALL COMMON AREAS.
  
 THE BATHROOMS COMMON MUST MEET TURNING
 REQUIREMENTS AS WELL AS THE HANDICAPPED
 UNIT.
  
 23) 11-4.1.3(1) AT LEAST ONE ACCESSIBLE
 ROUTE COMPLYING WITH 11-4.3 SHALL
 CONNECT ACCESSIBLE BUILDING OR FACILITY
 ENETRANCES WITH ALL ACCESSIBLE SPACES
 AND ELEMENTS WITHIN THE BUILDING OR
 FACILITY.
  
 24) 11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIABLE
 GRADE LEVEL.
  
 25)11-4.1.6(H) IF A PARTICULAR
 ENTRANCE IS NOT MADE ACCESSIBLE, APPRO-
 PRIATE ACCESSIBLE SIGNAGE INDICATING THE
 LOCATION OF THE NEAREST ACCESSIBLE
 ENTRANCE(S) SHALL BE INSTALLED AT OR
 NEAR THE INACCESSIBLE ENTRANCE, SUCH
 THAT A PERSON WITH DISABILITIES WILL
 NOT BE REQUIRED TO RETRACE THE APPROACH
 ROUTE FROM THE INNACCESSIBLE ENTRANCE.
  
 26)11-4.8.2 SLOPE & RISE. THE LEAST
 POSSIBLE SLOPE SHALL BE USED FOR ANY
 RAMP. THE MAXIMUM SLOPE FOR A RAMP IN
 NEW CONSTRUCTION SHALL BE 1 TO 12. THE
 MAXIMUM RISE FOR RUN SHALL BE 30" (SEE
 FIGURE 16).
  
 27)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 28) 11-4.13.5 DOORWAYS, MINIMUM
 CLEAR WIDTH: DOORWAY SHALL HAVE A MINI-
 MUM CLEAR OPENING OF 32" WITH THE DOOR
 OPEN 90 DEGREES, MEASURED BETWEEN THE
 FACE OF THE DOOR AND THE OPPOSITE STOP.
  
 29)11.4.3.11AREAS OF RESCUE ASSISTANCE
 INDICATE LOCATION AND CONSTRUCTION TYPE
 FOR AREAS OF REFUGE, INDICATE ON PLAN
 WHICH CASE USED (1-7).
  
 30)11-4.3.11.2 STAIRWAY WIDTH, EACH
 STAIRWAY ADJACENT TO AN AREA OF RESCUE
 SHALL HAVE A MINIMUM CLEAR WIDTH OF
 48" BETWEEN HANDRAILS.
  
 31)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIP-
 TION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND, WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 COOPERATION .
 JIM WITMER
 PLAN REVIEW
 (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 JIM WITMER
 BUILDING PLAN REVIEW