Plan Review Notes
Plan Review Notes For Permit 03071184
Permit Number 03071184
Review Stop P
Sequence Number 2
Notes
Date Text
2003-08-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT 2 MANUF. SPEC. SHEETS REQUIRED.
 PUMP SHALL BE LABELED PER SEC 303.4
 SHEETS SHALL SHOW LISTING BY APPROVED
 TESTING AGENCY.SECTION 303.4
 2) PUMP DISCHARGE LINE SHALL BE INSTALL-
 ED WITH A CHECK VALVE AND SHUT OFF
 VALVES ON DISCHARGE SIDE OF CHECK VALVE
 FOR SERVICE. SECTION 712.2
 3) PUMP TANK SHALL CONNECT INTO STANDARD
 VENT SYSTEM. SECTION 916.5.1
  
 REVIEW BY KEN STEVENS