2003-07-18 00:00:00DENIED:
 REFERENCE COMMENTS ON BUILDING PERMIT
 03040476.
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER 2001 FBC(M) TABLE 403.3.
  
 INDICATE SIZE AND MATERIAL OF THE O.A.
 DUCT.
  
 INTAKE LOUVER SHALL BE SCREENED PER 2001
 FBC(M) TABLE 401.6.PLEASE INDICATE
 SIZE OF INTAKE LOUVER.
  
 CONDENSER UNIT STAND SHALL COMPLY WITH
 2001 FBC TABLE 1511.7, SEE ATTACHED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.