Plan Review Notes
Plan Review Notes For Permit 03071134
Permit Number 03071134
Review Stop B
Sequence Number 2
Notes
Date Text
2003-09-03 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SUBMIT A SIGNED AND SEALED COPY OF
 A SOIL BORING TEST REPORT AS REQUIRED BY
 FBC 1804.2.2.
  
 3) REVISE GLASS BLOCK NOTE #5 ON A12.
 THE GLASS BLOCK IS REQUIRED TO HAVE A
 UNIFORM FACE THICKNESS OF 0.25 INCH WHEN
 LOCATED WITHIN (3) FEET HORIZONTALLY OF
 THE STANDING OR WALKING SURFACE OF A
 BATHTUB, SHOWER, ETC. SEE FBC 2405.2.1
 AND 2405.2.2.
  
 4) THE "REDLINED" CHANGE TO THE NEGATIVE
 WINDLOAD PRESSURE FOR THE DOUBLE ENTRY
 DOORS ON THE WIND LOAD SCHEDULE ON A1 IS
 REQUIRED TO BE INITIALED AND DATED BY
 THE DESIGNER OF RECORD.
  
 5)SUBMIT A SIGNED AND SEALED COPY OF THE
 LETTER FROM KENEZEVICH AND ASSOCIATES
 ADDRESSING THE USE OF CALK-IN ANCHORS IN
 CONCRETE BLOCK. THE LETTER SHOULD
 INDICATE THE PSI OF THE BLOCK AS TESTED.
  
 6) PROVIDE ADDITIONAL INFORMATION FOR
 THE INSERT HEADER AT THE COVERED LANAI.
 SPECIFY HOW IT WILL BE ANCHORED FOR
 UPLIFT, HOW THE TRUSSES WILL BE ATTACHED
 TO THE HEADER, HOW THE HEADER WILL BEAR
 ON THE WALLS AT EACH END, ETC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714