Notes
Date Text
2003-08-13 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
  
 3) SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.2.2.
  
 4) THE GLASS BLOCK IN THE MASTER BATH
 AND BATH 2 ARE IN HAZARDOUS LOCATIONS
 AND ARE REQUIRED TO BE TEMPERED OR HAVE
 A UNIFORM FACE THICKNESS OF 0.25" PER
 FBC 2405.2.
  
 5) THE FULL BATH ON THE FIRST FLOOR IS
 REQUIRED TO HAVE A DOOR WITH A 29" CLEAR
 OPENING PER FBC 11-4.23.2.
  
 6) FBC 1609.4 DOES NOT ALLOW THE ONE-
 THIRD INCREASE IN THE STEEL CALCULATIONS
 FOR COMBINATION LOADS. PLEASE REVISE THE
 VALUES LISTED IN THE ANCHOR SCHEDULES ON
 SHEETS A7 AND A8 TO VALUES THAT DO NOT
 INCLUDE THIS INCREASE. SEE THE 2003 USP
 CATALOG.
  
 7) THE 10'X 8' SLIDING GLASS DOOR (M) IS
 NOT LISTED IN THE WINDLOAD SCHEDULE ON
 A1.
  
 8) THE OVERHEAD GARAGE DOOR PRODUCT
 APPROVAL DOES NOT MEET THE PRESSURES
 LISTED IN THE WINDLOAD SCHEDULE ON A1.
  
 9) THE SH35 WINDOWS (W) AND (Y) WILL
 REQUIRE 3/16" TEMPERED GLASS TO MEET THE
 SPECIFIED WINDLOADS ACCORDING TO THE
 PRODUCT APPROVAL THAT WAS SUBMITTED.
  
 10) THE PRODUCT APPROVAL FOR THE DOUBLE
 ENTRY DOOR DOES NOT MEET THE WINDLOAD
 PRESSURES LISTED ON THE PLANS.
  
 11) PLEASE REVIEW THE WINDLOAD PRESSURES
 ON THE PLANS THEY MAY BE HIGHER THAN
 NEEDED FOR EXPOSURE B.
  
 12) THE KEY PLAN AND SCHEDULE FOR THE
 STORM PANELS DO NOT MATCH THE PLANS.
 PLEASE CORRECT.
  
 13) THE PRODUCT APPROVAL FOR THE STORM
 PANELS LISTS THE MINIMUM PANEL LENGTH
 FOR DIRECT MOUNT INSTALLATIONS AS 46".
 THE SCHEDULE LISTS SMALLER LENGTHS.
 PLEASE CORRECT.
  
 14) THE CALK-IN ANCHORS ARE HI-LITED ON
 THE PRODUCT APPROVAL FOR HOLLOW CONCRETE
 BLOCK. THEY CAN NOT BE USED FOR HOLLOW
 CONCRETE BLOCK WITH C1 CONNECTION TYPE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714