Plan Review Notes For Permit 03071132 |
Permit Number |
03071132 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2004-08-03 00:00:00 | ****** UNSAT ************ | | | | 1 )NOTE: PLEASE LIST THE REQ'D ARC | | FAULT PROTECTED CURCUIT(S) ON PANEL | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | IN BEDROOMS ARE TO BE PROTECTED , | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | 2002 NEC 210.12B | | | | 2)NOTE: PLEASE SEE MISSING LICENSE #'S | | REQUIRED ON TITLE BLOCK. | | FAC 61G1-16.004, FS 481.219 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|