Plan Review Notes
Plan Review Notes For Permit 03071078
Permit Number 03071078
Review Stop E
Sequence Number 2
Notes
Date Text
2003-09-11 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE NOTES FROM REVIEW.
 PLEASE SEE THAT SOME NOTES WERE NOT
 ADRESSED.
  
 2)NOTE: PLEASE SEE THAT SOME OCP DEVICES
 SHOWN ON PANEL SCHEDULE HAVE NOW BEEN
 CHANGED TO 2POLE BRKRS FOR SINGLE POLE
 ITEMS?
  
 3)NOTE: PLEASE "LIST THE REQ'D ARC FAULT
 CIRCUITS ON PANEL SCHEDULES. 210.12
 NOT OUTLETS,, CIRCUITS.
 4)NOTE: PLEASE SEE THAT AIC RATING IS
 NOW SHOWN FOR FOR METER? NEEDS TO BE
 SHOWN FOR MAINS/ PANELS. 110.9/215.5
  
 5)NOTE: PLEASE SEE SERVICE AND NOTES
 FROM FIRST REVIEW. SERVICE IS STILL
 NOTED TO HAVE A 300A MAIN? BUTNONE
 SHOWN ON RISER OR PLANS.??
 PLEASE SEE CONDCUTORS ETC .
 PLEASE SEE ORIG COMMENTS.
 250.66/310.16/310.15/240ETC NEC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 PLEASE SEE ATTACHED LETTER WITH RESPECT
 TO DESIGN PROFESSIONALS. REQ'D PER FS
 553.80(2)(B).
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]