2003-09-25 00:00:00 | DENIED |
| |
| 1) FL BLD CODE 1804.2.2 QUESTIONABLE |
| SOILS, WHERE THE BEARING CAPACITY IS |
| NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| WHERE THE BEARING CAPACITY OF THE SOIL I |
| S NOT DEFINITEY KNOWN, OR IS IN QUESTION |
| THE BUILDING OFFICIAL MAY REQUIRE EXPLOR |
| ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| TO THE PERMISSIBLE SAFE BEARING |
| CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| CITY SHALL BE CERTIFIED BY A GEOTECH- |
| NICALREPORT FROM A DESIGN PROFESSIONAL P |
| ROPERLY LICENSED IN THE STATE OF |
| FLORIDA. PLEASE SUBMIT A SOIL BORING |
| TEST REPORT. |
| |
| 2) BOTH FBC 1609.4.3 AND ASCE 7-98 2.4.3 |
| DO NOT PERMIT INCREASES IN THE ALLOWABLE |
| STRESS FOR THE STEEL FOR THE TRUSS |
| CONNECTORS. THE EXCEPTIONS IN FBC |
| 1609.4.3 ALLOW INCREASES TO BE TAKEN FOR |
| MASONRY COMPONENTS (ACI530/ASCE5/TMS402) |
| AND HURRICANE PANELS AND ASCE 7-98 2.4.3 |
| ALLOWS IT ONLY IF THE INCREASE CAN BE |
| JUSTIFIED BY STRUCTURAL BEHAVIOR CAUSED |
| BY RATE OR DURATION OF LOAD. PLEASE |
| REVISE THE TRUSS ANCHOR SCHEDULE ON G1 |
| TO THE VALUES LISTED IN THE 2003 USP AND |
| SIMPSON (HIGH WIND ADDITION) WHICH DO |
| NOT INCLUDE A ONE-THIRD INCREASE ON THE |
| STEEL CALCULATIONS. ALSO SPECIFY THE |
| PROPER CONNECTOR STOCK OR MODEL NUMBER |
| FOR THE NUMBER OF FASTENERS THAT ARE |
| SPECIFIED. |
| |
| 3) SUBMIT A KEY PLAN AND INSTALLATION |
| SCHEDULE FOR THE STORM PANELS. THE |
| FOLLOWING INFORMATION IS REQUIRED: TYPE |
| AND SPACING OF ANCHORS, MOUNT TYPE, |
| CONNECTION TYPE, SHUTTER SPAN, AND |
| OPENING PRESSURE. THIS INFORMATION IS |
| REQUIRED FOR PLAN REVIEW OR A SEPARATE |
| PERMIT WILL BE REQUIRED. |
| |