Plan Review Notes
Plan Review Notes For Permit 03071078
Permit Number 03071078
Review Stop E
Sequence Number 1
Notes
Date Text
2003-07-30 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE SIZE GROUNDING ELECTRODE
 PER 250.66/ 310.15 #2 MIN
  
 2)NOTE: RISER MENTIONS, 300 MAIN W/ OCP
 BUT SHOWS WHAT APPEARS TO BE A GUTTER?
 PLEASE CLARIFY HOW A 300A MAIN FEEDS TO
 TWO 150A PANELS? PLEASE
  
 3)NOTE; PLEASE CORRELATE PLANS WITH
 RISER DIAGRAM. PLANS SHOW ONLY ONE PANEL
 AND NO MAIN? 215.5
  
 4)NOTE: PLEASE SHOW MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAIN TO PANELS
 250.110/SIZE PER 250.122
  
 5)NOTE: PLEASE SUBMIT AIC RATING FOR
 300A MAIN. 110.9
  
 6)NOTE: PLEASE CORRELATE OCPAND LOADS
 ON PANEL SCHEDULE. MICRO/ POOL PUMP/
 WELL PUMP ETC, SHOWN AS 2P50 W/ #6 AND
 1.5KW LOADS?? PLEASE ALSO SEE WASHER
 SHOWN AS 2P-50A?
  
 7)NOTE: PLEASE SEE 20A OCP FOR #14 AWG
 GEN LT CIRCUITS. 240, 300
  
 8)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE.
 210.12
  
 9)NOTE: PLEASE LIST THE REQ`D DEDICATED'
 BATH(S) CIRCUIT(S).210.52D, 210.11C.3
  
 10)NOTE: PLEASE SHOW GARAGERECEPT
 AS GFI/GFI PROTECTED PER 210.8
  
 11)NOTE: PLEASE SEE MISSING SD IN DEN
 THIS RM IS AN ADAPTABLE SLEEPING RM AND
 REQUIRE'S A SD INSIDE AND OUTSIDE
 NFPA-72 8-1.4.2
  
 12)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 13)NOTE: PLEASE SEE THAT ALL RECEPTS IN
 BATHS TO BE W/IN 3' OF SINKS.
 210-52D
  
 14)NOTE: PLEASE SEE LETTER ATTACHED FOR
 MISSING INFORMATION REQ`D ON TITLE
 BLOCK FOR ENGINEER OF RECORD.
 FS 471/ FAC 61G15-23.002
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]