Date |
Text |
2003-07-30 00:00:00 | *********** UNSAT **************** |
| |
| 1)NOTE: PLEASE SIZE GROUNDING ELECTRODE |
| PER 250.66/ 310.15 #2 MIN |
| |
| 2)NOTE: RISER MENTIONS, 300 MAIN W/ OCP |
| BUT SHOWS WHAT APPEARS TO BE A GUTTER? |
| PLEASE CLARIFY HOW A 300A MAIN FEEDS TO |
| TWO 150A PANELS? PLEASE |
| |
| 3)NOTE; PLEASE CORRELATE PLANS WITH |
| RISER DIAGRAM. PLANS SHOW ONLY ONE PANEL |
| AND NO MAIN? 215.5 |
| |
| 4)NOTE: PLEASE SHOW MISSING EQUIPMENT |
| GROUNDING CONDUCTORS FROM MAIN TO PANELS |
| 250.110/SIZE PER 250.122 |
| |
| 5)NOTE: PLEASE SUBMIT AIC RATING FOR |
| 300A MAIN. 110.9 |
| |
| 6)NOTE: PLEASE CORRELATE OCPAND LOADS |
| ON PANEL SCHEDULE. MICRO/ POOL PUMP/ |
| WELL PUMP ETC, SHOWN AS 2P50 W/ #6 AND |
| 1.5KW LOADS?? PLEASE ALSO SEE WASHER |
| SHOWN AS 2P-50A? |
| |
| 7)NOTE: PLEASE SEE 20A OCP FOR #14 AWG |
| GEN LT CIRCUITS. 240, 300 |
| |
| 8)NOTE: PLEASE LIST THE REQ`D ARC FAULT |
| PROTECTED CIRCUITS ON PANEL SCHEDULE. |
| 210.12 |
| |
| 9)NOTE: PLEASE LIST THE REQ`D DEDICATED' |
| BATH(S) CIRCUIT(S).210.52D, 210.11C.3 |
| |
| 10)NOTE: PLEASE SHOW GARAGERECEPT |
| AS GFI/GFI PROTECTED PER 210.8 |
| |
| 11)NOTE: PLEASE SEE MISSING SD IN DEN |
| THIS RM IS AN ADAPTABLE SLEEPING RM AND |
| REQUIRE'S A SD INSIDE AND OUTSIDE |
| NFPA-72 8-1.4.2 |
| |
| 12)NOTE: PLEASE SEE MISSING RECEPTS PER |
| 210.52 |
| |
| 13)NOTE: PLEASE SEE THAT ALL RECEPTS IN |
| BATHS TO BE W/IN 3' OF SINKS. |
| 210-52D |
| |
| 14)NOTE: PLEASE SEE LETTER ATTACHED FOR |
| MISSING INFORMATION REQ`D ON TITLE |
| BLOCK FOR ENGINEER OF RECORD. |
| FS 471/ FAC 61G15-23.002 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW.IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |