2004-05-08 00:00:00***********UNSAT ****************
  
 1)NOTE: PLEASE SEE SIZING OF AWG FOR
 AHU'S, SHOWS #10 W/ 60A OCP. PLEASE SEE
 310.16, 424.3B ETC.
 THIS HAS BEEN NOTED AND COMMENTED ON
 THE PREVIOUS 4-REVIEWS. PLANS HAVE
 STILL NOT BEEN CORRECTED. ONE SET
 OF PLANS ARE BEING RETAINED FOR POSSIBLE
 REVIEW BY THE FBPE'S .
 PLEASE CORRELATE LOAD CALCULATIONS AND
 PANEL SCHEDULES FOR A/C EQUIPMENT.
  
 PLEASE SUPPLY ADDITIONL NEW SETS FOR
 REVIEW WHEN REVISION IS RESUBMITTED.
  
 2)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
  
 3)NOTE: PLANS MUST BE SIGNED WITH A
 SIGNATURE FROM ENGINEER THAT CONTIANS
 A VISABLE FIRST AND LAST NAME. PLANS
 APPEARS TO HAVE INITIALS. IF THIS IS
 ACTUAL SIGNATURE, PLEASE SUBMIT A COPY
 OF LICENSE IN ORDER TO VERIFY LEGAL
 SIGNATURE. FS 471.025, FAC 61G15-23.002
 PER FBPE'S. THIS VERIFICATION CAN BE
 KEPT IN FILE FOR FUTURE PROJECTS.
 PLANS ALSO MUST BE DATED WHEN SIGNED BY
 ENGINEER. FS 471.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  