2004-05-08 00:00:00 | ***********UNSAT **************** |
| |
| 1)NOTE: PLEASE SEE SIZING OF AWG FOR |
| AHU'S, SHOWS #10 W/ 60A OCP. PLEASE SEE |
| 310.16, 424.3B ETC. |
| THIS HAS BEEN NOTED AND COMMENTED ON |
| THE PREVIOUS 4-REVIEWS. PLANS HAVE |
| STILL NOT BEEN CORRECTED. ONE SET |
| OF PLANS ARE BEING RETAINED FOR POSSIBLE |
| REVIEW BY THE FBPE'S . |
| PLEASE CORRELATE LOAD CALCULATIONS AND |
| PANEL SCHEDULES FOR A/C EQUIPMENT. |
| |
| PLEASE SUPPLY ADDITIONL NEW SETS FOR |
| REVIEW WHEN REVISION IS RESUBMITTED. |
| |
| 2)NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| |
| |
| 3)NOTE: PLANS MUST BE SIGNED WITH A |
| SIGNATURE FROM ENGINEER THAT CONTIANS |
| A VISABLE FIRST AND LAST NAME. PLANS |
| APPEARS TO HAVE INITIALS. IF THIS IS |
| ACTUAL SIGNATURE, PLEASE SUBMIT A COPY |
| OF LICENSE IN ORDER TO VERIFY LEGAL |
| SIGNATURE. FS 471.025, FAC 61G15-23.002 |
| PER FBPE'S. THIS VERIFICATION CAN BE |
| KEPT IN FILE FOR FUTURE PROJECTS. |
| PLANS ALSO MUST BE DATED WHEN SIGNED BY |
| ENGINEER. FS 471.025 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |