Plan Review Notes
Plan Review Notes For Permit 03071076
Permit Number 03071076
Review Stop B
Sequence Number 5
Notes
Date Text
2003-11-10 00:00:00****PROVISO*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 SUBMIT A REVISION ADDRESSING:
  
 1.)PROVIDE A STRUCTURAL DETAIL FOR
 THE STAIRS, WITH FIREBLOCK TO COMPLY
 WITH FBC2305.1.SEE ATTACHED CODE
 REFERENCE AND NOTES. REVISE SHEET A6
  
 2.)WALL SECTIONS SAY "MATCH EXISTING"
 FOR SOFFIT VENTING; REMOVE THIS
 LANGUAGE AND REPLACE WITH CORRECT
 SOFFIT VENTING SCHEDULE AS PER
 CALCULATIONS.REVISE SHEET A6
  
 3.)REVISE WINDOW BUCK DETAIL, 2-G1,
 COMPLY WITH FBC1707.4.4.2, 2003 AMEND.
 REVISE SHEET G1.
  
 4.)REVISE DETAIL 4-G1 OR PROVIDE SPEC
 SHEET OR TECHNICAL BULLETIN FROM MFGR.
 HC10 NOT IN USP CATALOG; HC IS A WOOD-TO
 -WOOD CONNECTOR, CANNOT USE IN WOOD-TO-
 MASONRY APPLICATION UNLESS APPROVED BY
 MANUFACTURER.REVISE SHEET G1
  
 5.)REMOVE TRUSS ANCHOR SCHEDULE AND
 NOTE REGARDING STRESS INCREASE FOR STEEL
 FOR SHEET A5.REVISE SHEET A5, G1.