Plan Review Notes For Permit 03071076 |
Permit Number |
03071076 |
|
Review Stop |
B |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2003-11-10 00:00:00 | ****PROVISO***** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 | | | | SUBMIT A REVISION ADDRESSING: | | | | 1.)PROVIDE A STRUCTURAL DETAIL FOR | | THE STAIRS, WITH FIREBLOCK TO COMPLY | | WITH FBC2305.1.SEE ATTACHED CODE | | REFERENCE AND NOTES. REVISE SHEET A6 | | | | 2.)WALL SECTIONS SAY "MATCH EXISTING" | | FOR SOFFIT VENTING; REMOVE THIS | | LANGUAGE AND REPLACE WITH CORRECT | | SOFFIT VENTING SCHEDULE AS PER | | CALCULATIONS.REVISE SHEET A6 | | | | 3.)REVISE WINDOW BUCK DETAIL, 2-G1, | | COMPLY WITH FBC1707.4.4.2, 2003 AMEND. | | REVISE SHEET G1. | | | | 4.)REVISE DETAIL 4-G1 OR PROVIDE SPEC | | SHEET OR TECHNICAL BULLETIN FROM MFGR. | | HC10 NOT IN USP CATALOG; HC IS A WOOD-TO | | -WOOD CONNECTOR, CANNOT USE IN WOOD-TO- | | MASONRY APPLICATION UNLESS APPROVED BY | | MANUFACTURER.REVISE SHEET G1 | | | | 5.)REMOVE TRUSS ANCHOR SCHEDULE AND | | NOTE REGARDING STRESS INCREASE FOR STEEL | | FOR SHEET A5.REVISE SHEET A5, G1. |
|