Plan Review Notes
Plan Review Notes For Permit 03071076
Permit Number 03071076
Review Stop E
Sequence Number 4
Notes
Date Text
2003-11-06 00:00:00*************** NOTES REDLINED *****
  
 1)NOTE: PLEASE SEE PANEL SCHEDULE AND
 LOAD CALCULATIONS.
 AHU'S SHOWN WITH 60A OCP WITH #10 AWG
 AND 30A OCP W/ #6 AWG. PLEASE ALSO SEE
 LOAD CALCS DO NOT INCLUDE ALL A/C LOAD
 SHOWN?? TOTAL OF 3-10KW AND ONE 8KW.
  
 PLEASE SEE THAT PER FBPE PLANS SHOULD
 HAVE A COMPLETE SIGNATURE AS REQ'D UNDER
 FS 471.025. A VISBLE FIRST AND LAST
 NAME SHOULD SIGNED.
  
 PLEASE SEE THAT OLD PLAN WERE NOT TAKEN
 OUT OF SETS AND NEW SHEETS INSERTED AS
 REQUESTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION IS CALLED IN. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 DPALMER@WPB.
 THIS WILL REMAIN IN "F" STATUS UNTIL
 VERIFICATION CAN BE MADE THAT 4X FEE
 FOR PLAN WAS PAID. $1,407.20 WAS DUE
 BEFORE RESUBMITTING PLANS. NOTE WAS TAKE
 N OUT OF COMPUTER???
 OWES PER FS 553.80(2)(B).