Plan Review Notes For Permit 03071076 |
Permit Number |
03071076 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2004-05-25 00:00:00 | ******************DENIED**************** | | RETURN AIR IS NOT SIZED PROPERLY.PER | | 2001 FBC(M) 601.4, RETURN AIR SHALL BE | | EQUAL TO THE SUPPLY AIR TO THAT SPACE. | | | | AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | SEE ALSO COMMENT #3 BY DEWEY PALMER, | | ELECTRICAL PLAN REVIEW & KENNY STEVENS, | | PLUMBING PLAN REVIEW. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | PATTY KRAUSS/MECHANICAL PLAN REVIEW |
|