Date |
Text |
2003-10-09 00:00:00 | ************** UNSAT ************** |
| |
| PLEASE SEE THAT SOME NOTES FROM FIRST |
| TWO REVIEWS ARE NOT ADDRESSED. |
| PLEASE SEE THAT NOTICE WAS GIVEN TO |
| DESIGN PROFESSIONAL(S) ON LAST REVIEW |
| REQ'D UNDER FS 553.80(2)(B) |
| PLEASE SEE BZ RECEIPT ATTACH FOR FINE |
| REQ'D TO BE ASSESSED. THE FEE IS BASED |
| ON PLAN REVIEW PORTION OF PERMIT FEE, |
| WHICH IS 30% 4X. $1407.20 WHICH IS REQ'D |
| TO BE PAID BEFORE NEXT SUBMITTIAL. |
| |
| 2)NOTE: PLEASE SEE SERVICE ENT CONDUCTOR |
| -S STILL BEING SHOWN AT ONLY ONE SET OF |
| 3/0'S? THESE ARE RATED FOR A 225A, AS |
| PERMITTED UNDER 310.15B6. |
| LOAD FOR SERVICE ALONE IS OVER 300A'S. |
| THIS IS A 400A SERVICE. |
| |
| 3)NOTE: PREVIOUS NOTES REQUESTED INFO |
| ON TWO MAIN DISC'S SHOWN ARE NEW OR |
| EXISTING?, NOW MAINS ARE BEING SHOWN AS |
| EXSITING , YET NOTE FOR THESE MENTION; |
| IF REQ'D?? PLEASE CLARIFY IF NEW OR NOT? |
| |
| 4)NOTE: PLEASE SEE 250.66 FOR SIZING OF |
| GROUNDING ELECTRODE CONDCUTOR TO BE #2 |
| FOR A 400A SERVICE. |
| |
| 5)NOTE: PLEASE SEE PANEL SCHEDULE, |
| BATH CIRCUIT IS NOW NOTED AS BEING |
| RELOCATED? HOW IS THIS, IF BATH IS NEW? |
| |
| 6)NOTE: CORRELATE ALL AWG AND OCP ON |
| PANEL SCHEDULE. (DRYER) #12 AWG? |
| |
| 7)NOTE: PLEASE SEE MISSING GFI RECEPT |
| FOR NEW CU. 210.63 |
| |
| 8)NOTE: PLEASE SEE PANEL SCHEDULE B? |
| FIRST AHU IS NOTED AS BEING TWO AT 10KW? |
| |
| 9)NOTE: PLEASE SEE MISSING REQ'D COLD |
| WATER PIPE ON GROUNDING ELECTRODE.250.50 |
| |
| 10)NOTE: PLEASE SEE COPY OF FS 553.80(2) |
| (B) ATTACHED AGAIN. PLEASE SEE THAT IF |
| PLANS ARE NOT CORRECTED AND SUBMITTED |
| WITH ANY OF THE SAME COMMENTS NEXT TIME, |
| AN ADDITIONAL 4X FEE WILL BE ACCESSED |
| AND PLANS WILL BE REQ'D TO BE TURNED |
| INTO THE THE FBPE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |