2003-10-20 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)THE NOTICE OF COMMENCEMENT IS
 EXPIRED (OVER 90 DAYS, FS713.13).
  
 3.)SEE PREVIOUS CORRECTION LIST, ITEM
 #3, NOT ADDRESSED.PROVIDE A COPY OF
 THE RECEIPT SHOWING THAT IMPACT FEES
 HAVE BEEN PAID.
  
 4.)WALL SECTIONS STILL SAY "MATCH
 EXISTING", BUT A6 SHOWS THAT SOFFIT
 VENTS SHOULD BE 7X16 EVERY 12'.IS THIS
 THE EXISTING CONDITION?IF NOT, REVISE
 THE WALL SECTIONS.IF IT IS, MAKE A
 NOTE UNDER THE SOFFIT VENT CALCULATIONS.
  
 5.)SEE PREVIOUS CORRECTION LIST, ITEM
 #6.AS DISCUSSED, THE MANUFACTURER
 DOES NOT ALLOW STRESS INCREASE FOR
 STEEL.IF THIS WAS THE ONLY ITEM ON THE
 LIST, THE PERMIT WAS TO BE ISSUED WITH
 A PROVISO THAT THE CONNECTOR TABLES BE
 REVISED.AS THERE ARE OTHER ELECTRICAL
 AND STRUCTURAL CORRECTIONS, PLEASE
 REVISE AT THIS TIME.
  
 6.)SEE PREVIOUS LIST, ITEM #7, FIRE-
 BLOCK REQUIRED AT STAIRS,FBC2305.1.4(3).
 THE DETAIL SHOWN DOES NOT COMPLY WITH
 THE CODE.
  
 7.)SEE PREVIOUS CORRECTION LIST, ITEM
 #8; 2-G1 WAS NOT CHANGED.
  
 8.)SEE PREVIOUS LIST, ITEMS 10 AND 11,
 SHOW COMPLIANCE WITH FBC1608.2.
  
 9.)SEE PREVIOUS LIST, ITEM 12, NOT
 ADDRESSED.MULLION PRODUCT APPROVALS
 ARE STILL STAPLED TO THE PLAN; STILL DO
 NOT SEE WHERE MULLIONS ARE USED ON THIS
 JOB.HOWEVER, THE OTHER PRODUCT
 APPROVALS REQUESTED ARE STILL NOT A PART
 OF THIS PACKAGE.WINDOWS AND IMPACT
 PROTECTION WILL REQUIRE A SEPARATE
 PERMIT IF PRODUCT APPROVALS ARE NOT
 SUBMITTED.
  
 10.) ADDITIONAL FEES DUE.
  
 11.) THERE IS A MECHANICAL PROVISO ON
 THE MECHANICAL PAGE.PLEASE ADDRESS
 AT THIS TIME, PER REQUEST OF THE
 MECHANICAL PLAN REVIEWER.
  
 WHEN RESUBMITTING, REPLACE SHEETS WHICH
 HAVE CHANGED WITH THE NEW SHEETS. SUBMIT
 THE OLD SHEETS SEPARATELY, CLEARLY
 MARKED.TO EXPEDITE PLAN REVIEW,
 INCLUDE A TRANSMITTAL SHEET EXPLAINING
 HOW EACH ITEM WAS ADDRESSED.