Plan Review Notes
Plan Review Notes For Permit 03071076
Permit Number 03071076
Review Stop M
Sequence Number 2
Notes
Date Text
2003-10-16 00:00:00PROVISO:
 1.PLEASE NOTE RETURN AIR NOT SIZED
 PROPERLY.PLEASE REVISE TO COMPLY WITH:
 PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 2.SUPPLY DUCT NOT SIZED BETWEEN THE
 UNIT AND DISTRIBUTION BOX.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.