Plan Review Notes For Permit 03071076 |
Permit Number |
03071076 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-07-24 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | | | 1) POWDER ROOM SHALL NOT DRAIN THROUGH | | THE VENT FOR THE WASH MACHINE/LAUNDRY | | SINK. SECTION 908.3 READS IN PART. WHERE | | THE FIXTURE DRAINS CONNECT AT DIFFERENT | | LEVELS, THE VENT SHALL CONNECT AS A | | VERTICAL EXTENSION OF THE VERTICAL DRAIN | | THE UPPER FIXTURE SHALL NOT BE A WATER | | CLOSET. POWDER ROOM SHALL TIE IN DOWN- | | STREAM OF THE LAUNDRY ROOM FIXTURES. SEE | | RED LINE CORRECTIONS. | | 2) DATE REQUIRED ON SIGNATURE AND SEAL | | BY ENGINEER. SEE ATTACHED SHEET FOR ANY | | OTHER REQUIREMENTS PER 61G1-16 SEALS AND | | PLANS. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|