Plan Review Notes For Permit 03071076 |
Permit Number |
03071076 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-07-24 00:00:00 | *************** UNSAT ************** | | | | 1)NOTE: PLEASE SEE ATTACHED COPY OF FAC | | 61G1-16.004 FOR MISSING INFORMATION ON | | TITLE BLOCK. | | | | 2)NOTE: PLEASE INCLUDE SD REQ'D ON | | FIRST FLR LEADING TO FLR ABOVE. NFPA-72 | | 8-1.4.2 | | | | 3)NOTE: PLEASE CLARIFY/SHOW REQ'D RECEPT | | FOR A/ COND UNIT(S). 210.63 | | | | 4)NOTE: PLEASE LIST THE REQ'D DEDICATED | | BATH CIRCUIT(S) PER 210.11.C.3/ 210.52D | | #12, 20A | | | | 5)NOTE: PLEASE SEE MANY ITEMS ON | | PANEL SCHEDULE WHERE OCP/WIRE/ AND LOADS | | DO NOT CORRELATE. PLEASE ADJUST. | | 10KW ON 2-P 30'S, 1-P-20'S FOR AHU'S ETC | | | | 6)NOTE: PLEASE CLARIFY IF DISC'S SHOWN | | FOR SERVICE ARE GOING TO BE NEW? | | PANELS ARE SHOWN AS EXISTING. | | AS PER LOCAL AMENDMENTS 210-70, NO MORE | | THAN 8' OF UNPROTECTED CONDUCTORS INSIDE | | BLDG. | | PLEASE ALSO SUBMIT AIC RATINGS FOR MAINS | | IF INDEED NEW. 110.9/215.5 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|