Plan Review Notes
Plan Review Notes For Permit 03071076
Permit Number 03071076
Review Stop B
Sequence Number 1
Notes
Date Text
2003-07-29 00:00:00******CORRECTIONS*******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC, FBC13-103.1.2.
  
 3.)PROVIDE THE RECEIPT TO SHOW PAYMENT
 OF THE IMPACT FEES TO PALM BEACH CO.
  
 4.)SOFFIT VENTS MUST COMPLY WITH
 FBC2309.7.
  
 5.)DRAFTSTOPPING REQUIRED; SHOW A
 SCHEDULE AND DETAIL, FBC705.3.
  
 6.)THE TRUSS ANCHOR SCHEDULE HAS
 VALUES FOR ATTACHMENTS WHICH EXCEED THE
 UPLIFT ALLOWED AS PER THE USP 2003
 CATALOG.SEE PP 6-7, USP CATALOG,
 REGARDING STRESS INCREASES FOR STEEL.
  
 7.)FIREBLOCK REQUIRED AT THE STAIRS,
 FBC2305.1.4(3).
  
 8.)WINDOW BUCK DETAIL DOES NOT COMPLY
 WITH FBC1707.4.4.2, 2003 REVISION (G1).
  
 9.)PROVIDE A STRUCTURAL DETAIL FOR
 THE STAIRS.
  
 10.) PROVIDE A DETAIL FOR THE HANDRAIL.
 RAIL IS TO COMPLY WITH FBC1608.2.1.
  
 11.) PROVIDE A DETAIL FOR THE GUARDRAIL;
 MUST COMPLY WITH FBC1608.2.2, FBC CH.10.
  
 12.)MULLION PRODUCT APPROVALS WERE
 SUBMITTED.THERE WEREN'T ANY DOUBLE
 WINDOWS ON THE PLAN.
  
 13.) SUBMIT ROOF PRODUCT APPROVALS, OR
 THEY MAY BE SUBMITTED WITH THE ROOF
 PERMIT APPLICATION.
  
 14.)ADDITIONAL FEES (VALUE ADJUSTMENT,
 RADON); $133.70