2003-07-18 00:00:00 | DENIED |
| REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| |
| A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| FORMATION REQUIRED FOR PLAN REVIEW |
| 1) FBC-2001 SEC 424.2.6.1 ENGINEERING |
| DESIGN, CONSTRUCTION AND WORKMANSHIP. |
| ANSI/NSPI-4 92, AND NSPI-5. (ADD TO |
| NOTES) |
| 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE |
| WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| NUMBER AND MANUF INFO FOR VAC LOCK. |
| (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) |
| 3) FBC-2001424.2.6.6.5 WHERE PROVIDED, |
| THE VACUUM OR PRESSURE CLEANER FITTING |
| SHALL BE LOCATED AT LEAST 6" AND NOT |
| GREATER THAN 12" BELOW THE MINIMUM OPER- |
| ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| THE SKIMMER. (DETAIL OR NOTES) |
| 4) FBC-2001424.2.7.1 POOL CIRCULATING |
| PUMPS SHALL BE EQUIPPED ON THE INLET |
| SIDE WITH AN APPROVED TYPE HAIR AND LINT |
| STRAINER WHEN USED WITH A PRESSURE FIL- |
| TER. (DETAIL) |
| 5) FBC-2001 424.2.7.2 PUMPS AND EQUIP- |
| MENT SHALL BE MOUNTED ON A SUBSTANTIAL |
| BASE IN A MANNER THAT WILL ELIMINATE |
| STRAIN ON PIPING. SLAB SHALL BE A NOMIN- |
| AL 4" THICK. (DETAIL) |
| 6) FBC-2001 424.2.9 WATER SUPPLY, LOCAL |
| ORD. #2853-95, BACKFLOW REQUIRED ON |
| WATER SERVICE. (ADD TO NOTES) |
| 7) FBC-2001 424.2.12.1 PRESSURE TESTS. |
| PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| TEST SHALL BE APPROVED FOR PVC PIPE AND |
| FITTINGS. (ADD TO NOTES) |
| 8) FBC-2001 424.2.13.2JOINTS AND CON- |
| NECTIONS, FBC PLMG SEC 605.21, PURPLE |
| PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| NOTES) |
| 9) FBC-2001 424.2.14.1 SWIMMING POOL |
| WATER HEATERS SHALL BEAR THE LABEL OF A |
| RECOGNIZED TESTING AGENCY. MANUFACTURE |
| SHEETS REQUIRED. (SUBMITTAL) |
| 10) FBC-2001 424.2.14.2 WATER RETENTION, |
| PROVIDE A POSITIVE MEANS OF RETAINING |
| WATER IN THE HEATER WHEN PUMP IS SHUT |
| OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) |
| 11) FBC-2001 424.2.14.4 CONNECTIONS, ALL |
| WATER HEATING EQUIPMENT SHALL BE INSTAL- |
| LED WITH FLANGES OR UNION CONNECTIONS |
| ADJACENT TO THE HEATER. (ADD TO NOTES) |
| 12) POOL LAY-OUT SHEET GENERAL SPECIFIC- |
| ATIONS NOTES STATES 2 JETS ON BENCH. |
| POOL LAYOUT AND PIPING SCHEMATIC DOES |
| NOT SHOW THESE JETS. PLEASE CLAIRFY. |
| 13) PIPING SCHEMATIC DOES NOT REFLECT |
| THE POOL LAYOUT. THERE IS NO VACUUM LINE |
| SHOWN ON SCHEMATIC. (VALVE REQD 424.2.8) |
| 14) NO VALVE SHOWN ON SKIMMER LINE. ALL |
| SUCTION LINES SHALL HAVE VALVES INSTALL- |
| ED PER SECTION 424.2.8.2 |
| |
| REVIEW BY KEN STEVENS |