2003-07-31 00:00:00 | BUILDING DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) ONE SET OF THE ENERGY CALCULATIONS IS |
| FOR THE WRONG MODEL. |
| |
| 3) PLEASE REVISE DETAIL 1 ON SHEET 4. |
| THE BUCK IS REQUIRED TO EXTEND BEYOND |
| THE INTERIOR FACE OF THE WINDOW OR DOOR |
| FRAME. SEE FBC 1707.4.4.2(GLITCH AMEND.) |
| |
| 4) SPECIFY THE SIZE OF THE COLUMN AT THE |
| REAR PORCH. |
| |
| 5) SPECIFY THE CONNECTOR FOR THE WOOD |
| BEAM AT THE REAR PORCH WHERE IT CONNECTS |
| TO THE WALL AT THE MASTER BED ROOM. |
| |
| 6) THE ENGINEER IS REQUIRED TO SIGN AND |
| SEAL THE STRUCTURAL PLAN SHEETS ON |
| WHICH HIS TITLE BLOCK APPEARS. SEE FAC |
| 61G15-23.002. |
| |
| 7) THE NORANDEX SITE SPECIFIC PRODUCT |
| APPROVALS ARE REQUIRED TO BE SEALED BY |
| THE DESIGNER OF RECORD. THE ENGINEER'S |
| NAME, ADDRESS AND NUMBER ARE REQUIRED TO |
| BE ON THE FORM. SEE FAC 61G15-23.002. |
| |
| 8) PLEASE REVIEW THE REQUIRED DESIGN |
| PRESSURES FOR THE GARAGE DOOR ON SHEET |
| 3C. THEY APPEAR TO BE INCORRECT. |
| |
| 9) THE PRESSURES FOR THE GARAGE DOOR ON |
| SHEET 3A ARE BOTH NEGATIVE. PLEASE |
| CORRECT. |
| |
| 10) THE PRODUCT APPROVALS FOR THE STORM |
| PANELS ARE ILLEGIBLE AND THE CIRCLED |
| INSTALLATION INFORMATION DOES NOT APPEAR |
| TO CORRESPOND WITH THE STORM PANEL |
| CONNECTION DETAILS ON SHEET TWO OF THE |
| PLANS. ONE OF THE KEY PLANS AND SCHEDULE |
| IS FOR ANOTHER MODEL. THE DRAWINGS HAVE |
| BEEN STAMPED BY THE ENGINEER FOR ONE |
| PERMIT ONLY. AN ORIGINAL SIGNED AND |
| SEALED COPY OF THE DRAWING IS REQUIRED. |
| |
| 11) THE TWO USP TA STRAPS LISTED AS A-4 |
| IN THE TRUSS CONNECTOR SCHEDULE HAVE AN |
| UPLIFT VALUE OF 1230# ON A 1 PLY TRUSS. |
| PLEASE REVISE. FBC 1609.4 NO LONGER |
| ALLOWS A ONE-THIRD INCREASE IN THE |
| STEEL CALCULATIONS OF CONNECTORS. PLEASE |
| REVIEW THE VALUES LISTED AND REVISE IF |
| REQUIRED. SEE FBC 1609.4 AND 2003 USC |
| CATALOG. |
| |
| 12) SURVEY INCORRECTLY LISTS FLOOD ZONE |
| AS B. CITY RECORDS SHOW THAT PROPERETY |
| IS IN AN AO FLOOD ZONE. PLEASE CORRECT. |
| AN ELEVATION CERTIFICATE WILL BE |
| REQUIRED. |
| |