Plan Review Notes
Plan Review Notes For Permit 03070452
Permit Number 03070452
Review Stop B
Sequence Number 1
Notes
Date Text
2003-07-31 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) ONE SET OF THE ENERGY CALCULATIONS IS
 FOR THE WRONG MODEL.
  
 3) PLEASE REVISE DETAIL 1 ON SHEET 4.
 THE BUCK IS REQUIRED TO EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME. SEE FBC 1707.4.4.2(GLITCH AMEND.)
  
 4) SPECIFY THE SIZE OF THE COLUMN AT THE
 REAR PORCH.
  
 5) SPECIFY THE CONNECTOR FOR THE WOOD
 BEAM AT THE REAR PORCH WHERE IT CONNECTS
 TO THE WALL AT THE MASTER BED ROOM.
  
 6) THE ENGINEER IS REQUIRED TO SIGN AND
 SEAL THE STRUCTURAL PLAN SHEETS ON
 WHICH HIS TITLE BLOCK APPEARS. SEE FAC
 61G15-23.002.
  
 7) THE NORANDEX SITE SPECIFIC PRODUCT
 APPROVALS ARE REQUIRED TO BE SEALED BY
 THE DESIGNER OF RECORD. THE ENGINEER'S
 NAME, ADDRESS AND NUMBER ARE REQUIRED TO
 BE ON THE FORM. SEE FAC 61G15-23.002.
  
 8) PLEASE REVIEW THE REQUIRED DESIGN
 PRESSURES FOR THE GARAGE DOOR ON SHEET
 3C. THEY APPEAR TO BE INCORRECT.
  
 9) THE PRESSURES FOR THE GARAGE DOOR ON
 SHEET 3A ARE BOTH NEGATIVE. PLEASE
 CORRECT.
  
 10) THE PRODUCT APPROVALS FOR THE STORM
 PANELS ARE ILLEGIBLE AND THE CIRCLED
 INSTALLATION INFORMATION DOES NOT APPEAR
 TO CORRESPOND WITH THE STORM PANEL
 CONNECTION DETAILS ON SHEET TWO OF THE
 PLANS. ONE OF THE KEY PLANS AND SCHEDULE
 IS FOR ANOTHER MODEL. THE DRAWINGS HAVE
 BEEN STAMPED BY THE ENGINEER FOR ONE
 PERMIT ONLY. AN ORIGINAL SIGNED AND
 SEALED COPY OF THE DRAWING IS REQUIRED.
  
 11) THE TWO USP TA STRAPS LISTED AS A-4
 IN THE TRUSS CONNECTOR SCHEDULE HAVE AN
 UPLIFT VALUE OF 1230# ON A 1 PLY TRUSS.
 PLEASE REVISE. FBC 1609.4 NO LONGER
 ALLOWS A ONE-THIRD INCREASE IN THE
 STEEL CALCULATIONS OF CONNECTORS. PLEASE
 REVIEW THE VALUES LISTED AND REVISE IF
 REQUIRED. SEE FBC 1609.4 AND 2003 USC
 CATALOG.
  
 12) SURVEY INCORRECTLY LISTS FLOOD ZONE
 AS B. CITY RECORDS SHOW THAT PROPERETY
 IS IN AN AO FLOOD ZONE. PLEASE CORRECT.
 AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714