Plan Review Notes
Plan Review Notes For Permit 03070443
Permit Number 03070443
Review Stop B
Sequence Number 2
Notes
Date Text
2003-09-08 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE SURVEY INDICATES THE STRUCTURE IS
 LOCATED IN A "B" ZONE. THE CITY'S RECORD
 INDICATES THAT IT IS IN AN "AO" ZONE.
 PLEASE CORRECT THE SURVEY.
  
 3) SHEET 2 OF THE PLANS CONTAINS
 STRUCTURAL INFORMATION AND THE TITLE
 BLOCK OF THE ENGINEER. THE ENGINEER IS
 REQUIRED TO SIGN AND SEAL THIS SHEET.
 SEE FAC 61G15-23.002.
  
 4) THE REVISED DETAIL 1 ON SHEET 4, IS
 STILL INCORRECT. FBC 1707.4.4.2 REQUIRES
 THE BUCK TO EXTEND BEYOND THE INTERIOR
 FACE OF THE WINDOW OR DOOR FRAME SUCH
 THAT FULL SUPPORT OF THE FRAME IS
 PROVIDED.
  
 5) THE NORANDEX SITE SPECIFIC PRODUCT
 APPROVALS ARE REQUIRED TO BE SEALED BY
 THE DESIGNER OF RECORD. IF THE DESIGNER
 OF RECORD DOES NOT WISH TO SEAL THE FORM
 A SIGNED AND SEALED LETTER FROM THE
 DESIGNER SPECIFYING THE PRODUCT AND THE
 LOCATION OF THE STRUCTURE, STATING THAT
 THE PRODUCT HAS BEEN REVIEWED AND IS
 ACCEPTABLE FOR USE IN THE STRUCTURE.
  
 6) THE PRODUCT APPROVAL FOR THE STORM
 PANELS ARE ILLEGIBLE. SUBMIT CLEAR
 COPIES. THE DRAWINGS FOR THE STORM
 PANELS HAVE A STAMP ON THEM THAT
 INDICATES THEY ARE FOR ONE PERMIT ONLY.
 THIS MEANS THAT A SIGNED AND SEALED
 COPY OF THE DRAWINGS IS REQUIRED FOR
 EACH PERMIT. SUBMIT A KEY PLAN AND
 INSTALLATION SCHEDULE FOR THE STORM
 PANELS.
  
 7) THE PRODUCT APPROVAL FOR THE OUTSWING
 DOOR WITH A SIDELITE IS ILLEGIBLE.
 SUBMIT CLEAR COPIES ALONG WITH THE
 APPROVED DRAWINGS (# S-2188).
  
 IF YOU HAVE QUESTIONS, PLEASE CALL.
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714