Plan Review Notes
Plan Review Notes For Permit 03070443
Permit Number 03070443
Review Stop B
Sequence Number 1
Notes
Date Text
2003-07-31 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE SURVEY INCORRECTLY LISTS FLOOD
 ZONE AS B. CITY RECORDS SHOW THAT THE
 PROPERTY IS LOCATED IN AN "AO" FLOOD
 ZONE. PLEASE CORRECT. AN ELEVATION
 CERTIFICATE WILL BE REQUIRED.
  
 3) FBC 1609.4 NO LONGER ALLOWS THE ONE-
 THIRD INCREASE IN THE STEEL CALCULATIONS
 FOR TRUSS CONNECTORS. THE TRUSS ANCHOR
 SCHEDULE ON SHEET 2 LISTS INCORRECT
 UPLIFT VALUES. PLEASE REVISE.
 THE "USP" RT STRAPS REQUIRE THE NAILS TO
 BE EQUALLY DISTRIBUTED ON BOTH SIDES OF
 THE CONNECTION. SEE 2003 USP CATALOG.
  
 4) SHEET 2 WHICH CONTAINS STRUCTURAL
 INFORMATION AND THE ENGINEER'S TITLE
 BLOCK IS NOT SIGNED AND SEALED BY THE
 ENGINEER. FAC 61G15-23.002
  
 5) PLEASE REVISE DETAIL 1 ON SHEET 4.
 THE BUCK IS REQUIRED TO EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME. SEE FBC 1707.4.4.2(GLITCH AMEND.)
  
 6) SPECIFY THE SIZE OF THE COLUMN AT THE
 REAR PORCH.
  
 7) SPECIFY THE CONNECTOR FOR THE WOOD
 BEAM AT THE REAR PORCH WHERE IT CONNECTS
 TO THE WALL AT THE MASTER BEDROOM.
  
 8) THE ENERGY CALCULATIONS DO NOT STATE
 THAT THEY ARE WORST CASE AND THEREFORE
 CAN NOT BE USED GENERICALLY, DUE TO THE
 DIFFERENT ORIENTATIONS OF THE STRUCTURES
 ON THE LOTS. PLEASE CORRECT. SEE FBC
 CHAPTER 13.
  
 9) THE NORANDEX SITE SPECIFIC PRODUCT
 APPROVALS ARE REQUIRED TO BE SEALED BY
 THE DESIGNER OF RECORD. THE ENGINEER'S
 NAME, ADDRESS AND NUMBER ARE REQUIRED TO
 BE ON THE FORM. SEE FAC 61G15-23.002.
  
 10) PLEASE REVIEW THE LISTED DESIGN
 PRESSURES FOR THE GARAGE DOOR ON SHEET
 3C, THEY APPEAR TO BE INCORRECT.
  
 11) THE PRESSURES FOR THE GARAGE DOOR ON
 SHEET 3A ARE BOTH NGATIVE. PLEASE
 CORRECT.
  
 12) THE PRODUCT APPROVALS FOR THE STORM
 PANELS ARE ILLEGIBLE AND TH CIRCLED
 INSTALLATION INFORMATION DOES NOT APPEAR
 DOES NOT APPEAR TO CORRESPOND WITH THE
 STORM PANEL CONNECTION DETAILS ON SHEET
 2 OF THE PLANS. THE STORM PANEL DRAWINGS
 ARE STAMPED FOR ONE PERMIT ONLY. AN
 ORIGINAL SIGNED AND SEALED COPY OF THE
 DRAWING IS REQUIRED. SUBMIT KEY PLAN AND
 INSTALLATION SCHEDULE.
  
 13) THE PRODUCT APPROVAL FOR THE OUT-
 SWING DOOR WITH SIDELITE IS ILLEGIBLE.
 SUBMIT CLEAR COPIES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714