Date |
Text |
2003-08-06 00:00:00 | DENIED |
| |
| 1) 1001.1.3/ 1005.4 ZERO LOT LINE |
| EGRESS:WHEN ACCESS TO OR FROM A RE- |
| QUIRED EMERGENCY ESCAPE AND RESCUE OPEN- |
| ING OF A STRUCTURE TO THE PUBLIC WAY, |
| REQUIRES TRANSVERSING A PROPERTY |
| (ADJOINING LOT) THAT IS NOT PART OF THE |
| ONE WHICH THE STRUCTURE IS LOCATED, AN |
| EGRESS EASEMENT THROUGH THE ADJOINING |
| PROPERTY IS REQUIRED AND SHALL BE RECORD |
| ED IN THE COUNTY RECORDS. THIS EASEMENT |
| SHALL BE A MINIMUM OF 3' WIDE AND NOTH- |
| ING SHALL BE PLACED WITHIN THE EASEMENT |
| AREA WHICH WOULD BLOCK ACCESS TO THE |
| EASEMENT AND OR IMPEDE EMERGENCY EGRESS |
| FROM THE RESCUE OPENING TO THE PUBLIC |
| WAY. NO LANDSCAPING, FENCES OR OTHER |
| IMPEDIMENTS SHALL BE INSTALLED IN THIS |
| EASEMENT. SUBMIT RECORDED COPY OF THE |
| SUBDIVISION COVENANTS SPECIFYING AN |
| EGRESS EASEMENT. |
| |
| 2) FBC 1909.3 REQUIRES THE WWM IN THE |
| SLAB TO BE SUPPORTED ON APPROVED |
| MATERIALS AT NO MORE THAN 3'OC. PLEASE |
| INDICATE ON PLANS. |
| |
| 3) THE GLASS BLOCK AT THE MASTER BATH |
| TUB IS IN A HAZARDOUS LOCATION AND IS |
| REQUIRED TO HAVE A MINIMUM UNIFORM FACE |
| THICKNESS OF 0.25" PER FBC 2405.2. |
| PLEASE SPECIFY ON THE PLANS. |
| |
| 4) THE DOOR IN THE GARAGE WALL ADJACENT |
| TO THE CONDITIONED SPACE IS REQUIRED TO |
| BE SOLID CORE OR INSULATED BY FBC |
| CHAPTER 13. |
| |
| 5) THE WINDOWS IN THE DEN EXCEED THE 20 |
| PERCENT OF WALL ALLOWED AS OPENINGS BY |
| FBC TABLE 600. (21SQFT ALLOWED) |
| |
| 6) THE LETTER FROM THE ENGINEER FOR THE |
| GLASS BLOCK IS REQUIRED TO BE SIGNED AND |
| SEALED WHEN SUBMITTED FOR PUBLIC RECORD |
| PER FAC 61G15-23.002. |
| |
| 7) FBC 1609.4.3 DOES NOT ALLOW THE ONE- |
| THIRD INCREASE ON STEEL CALCULATIONS FOR |
| CONNECTORS. PLEASE REVISE THE CONNECTOR |
| SCHEDULE ON SHEET TO VALUES WHICH DO NOT |
| INCLUDE THIS INCREASE. SEE THE 2003 USP |
| AND SIMPSON HIGH WIND-RESISTANT CONST. |
| CATALOGS. |
| |
| 8) HUGHES WAS PURCHASED BY USP SO TIME |
| AGO. PLEASE UPDATE THE HUGHES CONNECTORS |
| SPECIFIED ON SHEET 6 AND IN THE DETAILS |
| ON SHEET 8 TO A CURRENT MANUFACTURER. |
| |
| 9) PLEASE REVISE THE BUILDING CATEGORY |
| ON SHEET 6 TO CATEGORY II. SEE TABLE 1-1 |
| IN ASCE 7-98. R3 IS THE OCCUPANCY |
| CLASSIFICATION. |
| |
| 10) NOTE 10 ON SHEET 8 REFERENCES THE |
| WRONG CODE. PLEASE UPDATE TO 2001 FBC. |
| |
| 11) PROVIDE A DETAIL FOR STRUCTURAL 2X |
| BUCKS AS REQUIRED BY THE PRODUCT |
| APPROVAL FOR THE ENTRY DOOR. |
| |
| 13) FBC 1005.4.5 (GLITCH AMENDMENTS) |
| REQUIRES AT LEAST ONE MEANS OF ESCAPE |
| FROM A DWELLING WHEN SHUTTERED FOR |
| IMPACT PROTECTION. THE MEANS OF ESCAPE |
| SHALL BE WITHIN THE FIRST FLOOR OF THE |
| DWELLING AND CAN NOT BE LOCATED IN A |
| GARAGE. OCCUPANTS IN ANY PART OF THE |
| DWELLING SHALL HAVE ACCESS TO IT WITHOUT |
| HAVING TO PASS THROUGH A LOCKABLE DOOR |
| NOT UNDER THEIR CONTROL. INDICATE HOW |
| COMPLIANCE WILL BE ACHIEVED. |
| |
| 14) THERE ARE TWO ARCHITECT'S TITLE |
| BLOCKS ON SOME OF THE PLAN SHEETS. |
| PLEASE REMOVE THE ONE THAT DOES NOT |
| BELONG TO THE DESIGNER OF RECORD. |
| |
| 15) STORM PANELS : THE SAFEGUARD COMPANY |
| IS NO LONGER IN BUSINESS AND WEATHER- |
| GUARD HAS NOT COMPLETED THE PROCESS OF |
| ASSUMING THE PRODUCT APPROVAL FROM SBCCI |
| THE BUILDING OFFICIAL HAS DETERMINED |
| THAT WE CAN NOT ACCEPT THIS PRODUCT FOR |
| USE IN THE CITY OF WPB AT THIS TIME. |
| |
| 16) THE TRUSS DRAWINGS AND LAYOUT FOR |
| SINGLE FAMILY DWELLINGS ARE NO LONGER |
| REQUIRED TO BE SUBMITTED FOR PLAN REVIEW |
| THEY ARE TO BE GIVEN TO THE INSPECTOR IN |
| THE FIELD AT THE TRUSS INSPECTION. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |