Plan Review Notes
Plan Review Notes For Permit 03070117
Permit Number 03070117
Review Stop P
Sequence Number 1
Notes
Date Text
2003-07-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHOW CLEAR FLOOR SPACE FOR ALL HDCP
 FIXTURES. W/C'S 11-4.16.2, LAV'S 4.19.3,
 URNAL 4.18.3, BRK RM SINK 4.24.5.
 2) SUBMIT DETAIL FOR BREAK ROOM SINK.
 SHOW COMPLIANCE WITH 11-4.24 AND ALL
 SUBSECTIONS.
 3) DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE OF THE TURNING CIRCLE. SEC
 11-4.22.2. (TOILET ROOM BY BRK RM)
 4) SHOW TURNING CIRCLES IN TOILET ROOMS.
 THEY ARE NOT REQUIRED IN STALLS. SECTION
 11-4.22.3
 5) SHTS A-3.0 & A-3.2, SANITARY PLUMBING
 PLAN AND SANITARY RISER DIAGRAM. SECTION
 909.1, ONLY THE FIXTURES WITHIN THE BATH
 ROOM GROUP SHALL CONNECT TO THE WET-
 VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. - THE BREAK
 ROOM SINK SHALL TIE IN DOWNSTREAM OF THE
 BATHROOM GROUP.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692