Plan Review Notes
Plan Review Notes For Permit 03070117
Permit Number 03070117
Review Stop E
Sequence Number 1
Notes
Date Text
2003-07-17 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE W/ PANEL SCHEDULE(S).
 PLEASE CLARIFY NOTE MENTION ALL FIXTURES
 BEING FED THROUGH CONTACTOR EXCEPT
 NIGHT LITES. ? EXIT AND EM LT WON'T BE
 FED THIS WAY? PLEASE SEE 700-12E FOR
 CIRCUITING THESE FIXTURES.
  
 2)NOTE: PLEASE SHOW RECEPTS FOR ROOFTOP
 EQUIPMENT AS GFI. 210-63/210-8
  
 3)NOTE: PLEASE SHOW MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAINS AND
 PANELS. 250-110/250-122
  
 4)NOTE: PLEASE SHOW AIC RATINGS FOR ALL
 NEW EQUIPMENT BEING INSTALLED. MAINS/
 PANELS/BRKRS ARE ALL TO BE RATED FOR THE
 AVAILABLE FUALT CURRENT. 110-9
  
 5)NOTE: PLEASE SHOW SIZING OF CONDUCTORS
 FROM GUTTER TO MAINS.215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]