Plan Review Notes For Permit 03070117 |
Permit Number |
03070117 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-07-17 00:00:00 | *************** UNSAT **************** | | | | 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS | | AND CORRELATE W/ PANEL SCHEDULE(S). | | PLEASE CLARIFY NOTE MENTION ALL FIXTURES | | BEING FED THROUGH CONTACTOR EXCEPT | | NIGHT LITES. ? EXIT AND EM LT WON'T BE | | FED THIS WAY? PLEASE SEE 700-12E FOR | | CIRCUITING THESE FIXTURES. | | | | 2)NOTE: PLEASE SHOW RECEPTS FOR ROOFTOP | | EQUIPMENT AS GFI. 210-63/210-8 | | | | 3)NOTE: PLEASE SHOW MISSING EQUIPMENT | | GROUNDING CONDUCTOR BETWEEN MAINS AND | | PANELS. 250-110/250-122 | | | | 4)NOTE: PLEASE SHOW AIC RATINGS FOR ALL | | NEW EQUIPMENT BEING INSTALLED. MAINS/ | | PANELS/BRKRS ARE ALL TO BE RATED FOR THE | | AVAILABLE FUALT CURRENT. 110-9 | | | | 5)NOTE: PLEASE SHOW SIZING OF CONDUCTORS | | FROM GUTTER TO MAINS.215-5 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|