2003-08-07 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) FBC 11-4.17.6 TOILET STALL GRAB BARS, |
| SHEET A-1.1.THE GRAB BAR ON THE SIDE |
| WALL SHALL BE MIN. 42" LONG AND |
| POSITIONED SO THAT THE FRONT END IS |
| MIN. 54" FROM THE REAR WALL.AMEND THE |
| PLAN VIEW OF 'TYPICAL H.C. RESTROOM' |
| (REF. FIG. 29). |
| |
| 2) FBC 11-4.19ACCESSIBLE LAVATORIES, |
| SHEET A-1.1.THE RIM OF THE LAVATORY |
| SHALL BE NO HIGHER THAN 34" ABOVE |
| FINISHED FLOOR LEVEL.THE HOT WATER AND |
| DRAIN PIPES UNDER THE LAVATORIES SHALL |
| BE INSULATED OR OTHERWISE CONFIGURED TO |
| PROTECT AGAINST CONTACT.ANNOTATE THE |
| 'TYPICAL H.C. RESTROOM' ELEVATION TO |
| DEMONSTRATE COMPLIANCE (REF. FIG. 31). |
| |
| 3) FBC 11-4.24BREAK ROOM, SHEET A-1.0. |
| THE BREAK ROOM SINK SHALL BE MOUNTED |
| WITH THE RIM NO HIGHER THAN 34" ABOVE |
| FINISHED FLOOR LEVEL WITH KNEE CLEARANCE |
| AT LEAST 27" HIGH, 30" WIDE AND 19" DEEP |
| UNDER THE SINK.THE SINK SHALL BE MAX. |
| 6-1/2" DEEP.ANY EXPOSED HOT WATER AND |
| DRAIN PIPES SHALL BE INSULATED OR |
| OTHERWISE CONFIGURED TO PROTECT AGAINST |
| CONTACT.ANNOTATE THE BREAK ROOM PLAN |
| TO DEMONSTRATE COMPLIANCE. |
| |
| 4) FBC 11-4.8.7NEW CONCRETE RAMP AND |
| LANDING.THE RAMP AND LANDING SHALL |
| HAVE CURBS (MIN. 2" HIGH - FIG. 17), |
| WALLS, RAILINGS OR PROJECTING SURFACES |
| AS EDGE PROTECTION.THE REQUIRED 18" |
| CLEARANCE SHOWN BETWEEN THE EDGE OF THE |
| LANDING AND THE LEADING EDGE OF THE DOOR |
| SHALL BE ADJUSTED AS NECESSARY TO |
| MAINTAIN MIN. 18" CLEAR BETWEEN THE |
| CURB, WALL ETC AND THE LEADING EDGE OF |
| THE DOOR. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| TELEPHONE: (561) 805 6716ROBERT BROWN |