2003-07-11 00:00:00DENIED
 REFERENCE: UNIFORM COUNTYWIDE SWIMMING
 POOL AND SPA CODE
  
 1) POOL OR SPA PIPING LAYOUT WITH ALL
 PIPE SIZES AND VALVES SHOWN. SECTION3(D)
 POOL PIPING SCHEMATIC DOES NOT REFLECT
 THE POOL LAYOUT. NO VACUUM LINE SHOWN
 ON SCHEMATIC.
 2) TURNOVER RATE REQUIRED. SECTION 3(E).
 3) TIME CLOCKS REQUIRED ON PRIVATE POOLS
 SECTION 33.
 4) POOL LAYOUT SHEET, ENGINEER SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS, &
 ENGINEERS NUMBER ON EACH SHEET. NO TITLE
 BLOCK SHOWN. ENGINEERS NUMBER NOT SHOWN
 ON ALL OTHER SHEETS. 61G15-23.003
  