Plan Review Notes For Permit 03070057 |
Permit Number |
03070057 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-08-20 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 03070057 | | ADD:8049 CRANE'S POINT | | CONT: NORTHSTAR | | TEL: (561)662-7700 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | ACTION: DENIED | | | | 1) WALL OPENING PRESSURE CHART FOR | | LOT# 35 NOT FOR LOT# 37. | | | | 2) PROVIDE THE SIGNED /SEALED CALS FOR | | THE BUTT GLASS. | | | | 3)1609.4.3 LOAD REDUCTION. | | WHEN STRUCTURAL EFFECTS DUE TO TWO OR | | MORE LOADS IN COMBINATION WITH DEAD LOAD | | ARE INVESTIGATED IN LOAD COMBINATIONS OF | | 1609.4.1 OR 1609.4.2, THE COMBINED | | EFFECTS DUE TO THE TWO OR LOADS MULTI- | | PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD | | LOADS SHALL NOT BE LESS THAN THE EFFECTS | | FROM THE LOAD COMBINATION OF THE DEAD | | LOAD PLUS THE LOAD PRODUCING THE LARGEST | | EFFECTS. INCREAS IN ALLOWABLE STRESS SPE | | CIFIED IN THE MATERIALS SECTIONS OF THIS | | CODE OR A REFRENCED STANDARD SHALL NOT | | BE USED WITH THESE LOAD COMBINATIONS | | EXCEPT THAT A DURATION OF LOAD INCREASE | | SHALL BE PERMITTED IN ACCORDANCE WITH | | CHAPTER 23. | | | | RE-EVALUATE TRUSS ANCHOR SCHEDULE. | | THE ANCHOR SCHEDULE ITSELF NEEDS TO BE | | RE-EVALUATED PLUS REASSIGNING WHAT MARK | | WILL BE USED PER STRAP | | | | 4) ADD REVISIONS TO REVISION COLUMN, | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|