2003-07-28 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| |
| 1) SHT A4 SANITARY RISER DIAGRAM DOES |
| NOT REFLECT THE FLOOR PLAN, NOR DOES IT |
| MEET CODE REQUIREMENTS. |
| - EXTRA BATHROOM ON SANITARY RISER NOT |
| SHOWN ON FLOOR PLAN. |
| - WASH MACHINE SHALL NOT DRAIN INTO THE |
| WET VENT OF BATHROOM #3 PER 909.1 - ALSO |
| THE LAV FOR BATHROOM #3 AND THE WASH |
| MACHINE ARE NOT LOCATED ON A COMMON WALL |
| - THE BIDET SHOWN ON THE SANITARY RISER |
| IS NOT SHOWN ON THE FLOOR PLAN. |
| 2) THE FOLLOWING ITEMS ARE REQUIRED FOR |
| APPLICATION FOR SEPARATE GAS PERMIT. |
| A. TYPE OF GAS, (LP OR NATURAL) |
| B. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| THRU 402.5.2 AND TABLES 402(1) THRU |
| 402(34). |
| C. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). |
| D. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| GAS CODE SECTION 304. |
| E. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| F. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| G. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND |
| APPURTENANCES PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| |