2003-07-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03070057
 ADD: CRANES POINTE WAY
 CONT: NORTHSTAR CUSTOM HOMES
 TEL: (561)799-7700
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) PROVIDE ENGINEERING CALCULATIONS FOR
 BUTT GLAZING AS PER FBC 2406.2. ENGINEER
 ING SHEET NOTES THERE COULS BE 1/2"
 DEFLECTION IN THE LENGHT OF GLASS BUT
 THE GLASS BITE IS ONLY 3/8", THIS WOULD
 ALLOW THE GLASS TO BE RELEASED FROM THE
 FRAME!
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE A MULLION CHART WHICH WILL GIVE
 THE SIZE OF THE MULLION AND THE DIREC-
 TION THE MULLION WILL BE USED.
  
 3) PLANS INDICATE THAT THE DESIGNER IS
 USING THE MORE STRINGENT WIND EXPOSURE
 CLASS"C" BUT THE PRESSURES DO NOT
 REFLECT THIS. SEE 2 EXAMPLES.
  
 4) PLANS ALSO INDICATE THE SIDELIGHTS AS
 WELL AS DOORS TO HAVE TEMPERED GLASS,
 IF SO, HOW WILL LARGE MISSLE IMPACT GLAZ
 ING BE USED?
  
 5) 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 6) 1609.4.3 LOAD REDUCTION.
 WHEN STRUCTURAL EFFECTS DUE TO TWO OR
 MORE LOADS IN COMBINATION WITH DEAD LOAD
 ARE INVESTIGATED IN LOAD COMBINATIONS OF
 1609.4.1 OR 1609.4.2, THE COMBINED
 EFFECTS DUE TO THE TWO OR LOADS MULTI-
 PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD
 LOADS SHALL NOT BE LESS THAN THE EFFECTS
 FROM THE LOAD COMBINATION OF THE DEAD
 LOAD PLUS THE LOAD PRODUCING THE LARGEST
 EFFECTS. INCREAS IN ALLOWABLE STRESS SPE
 CIFIED IN THE MATERIALS SECTIONS OF THIS
 CODE OR A REFRENCED STANDARD SHALL NOT
 BE USED WITH THESE LOAD COMBINATIONS
 EXCEPT THAT A DURATION OF LOAD INCREASE
 SHALL BE PERMITTED IN ACCORDANCE WITH
 CHAPTER 23.
 RE-EVALUATE TRUSS ANCHOR SCHEDULE, USP
 IS ELIMENATING THE TAPR216 IT IS NOT IN
 THE 2003 CATALOG. RE-EVALUATE TRUSS
 ANCHOR SCHEDULE.
  
 7) PLEASE PROVIDE RATIONAL ANALYSIS FOR
 THE BEAM ABOVE THE BUTT GLASS, ECENTRIC
 LOADING.
  
 8) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 ROOF FRAMING PLAN MISSING INFORMATION ON
 ROOF GIRDERS OVER THE COVERED PORCH
 AREA, SEE VALLEY, MISSING GIRDERS!!!!
 PROVIDE LOADS!
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026