2003-07-28 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03070057 |
| ADD: CRANES POINTE WAY |
| CONT: NORTHSTAR CUSTOM HOMES |
| TEL: (561)799-7700 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| ACTION: DENIED |
| |
| 1) PROVIDE ENGINEERING CALCULATIONS FOR |
| BUTT GLAZING AS PER FBC 2406.2. ENGINEER |
| ING SHEET NOTES THERE COULS BE 1/2" |
| DEFLECTION IN THE LENGHT OF GLASS BUT |
| THE GLASS BITE IS ONLY 3/8", THIS WOULD |
| ALLOW THE GLASS TO BE RELEASED FROM THE |
| FRAME! |
| |
| 2)FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| PROVIDE A MULLION CHART WHICH WILL GIVE |
| THE SIZE OF THE MULLION AND THE DIREC- |
| TION THE MULLION WILL BE USED. |
| |
| 3) PLANS INDICATE THAT THE DESIGNER IS |
| USING THE MORE STRINGENT WIND EXPOSURE |
| CLASS"C" BUT THE PRESSURES DO NOT |
| REFLECT THIS. SEE 2 EXAMPLES. |
| |
| 4) PLANS ALSO INDICATE THE SIDELIGHTS AS |
| WELL AS DOORS TO HAVE TEMPERED GLASS, |
| IF SO, HOW WILL LARGE MISSLE IMPACT GLAZ |
| ING BE USED? |
| |
| 5) 1707.4.4.2 TAPERED BUCKS: |
| SHALL EXTEND BEYOND THE INTERIOR FACE |
| OF THE WINDOW OR DOOR FRAME SUCH THAT |
| FULL SUPPORT OF THE FRAME IS SUPPORTED. |
| |
| 6) 1609.4.3 LOAD REDUCTION. |
| WHEN STRUCTURAL EFFECTS DUE TO TWO OR |
| MORE LOADS IN COMBINATION WITH DEAD LOAD |
| ARE INVESTIGATED IN LOAD COMBINATIONS OF |
| 1609.4.1 OR 1609.4.2, THE COMBINED |
| EFFECTS DUE TO THE TWO OR LOADS MULTI- |
| PLIED BY 0.75 PLUS EFFECTS DUE TO DEAD |
| LOADS SHALL NOT BE LESS THAN THE EFFECTS |
| FROM THE LOAD COMBINATION OF THE DEAD |
| LOAD PLUS THE LOAD PRODUCING THE LARGEST |
| EFFECTS. INCREAS IN ALLOWABLE STRESS SPE |
| CIFIED IN THE MATERIALS SECTIONS OF THIS |
| CODE OR A REFRENCED STANDARD SHALL NOT |
| BE USED WITH THESE LOAD COMBINATIONS |
| EXCEPT THAT A DURATION OF LOAD INCREASE |
| SHALL BE PERMITTED IN ACCORDANCE WITH |
| CHAPTER 23. |
| RE-EVALUATE TRUSS ANCHOR SCHEDULE, USP |
| IS ELIMENATING THE TAPR216 IT IS NOT IN |
| THE 2003 CATALOG. RE-EVALUATE TRUSS |
| ANCHOR SCHEDULE. |
| |
| 7) PLEASE PROVIDE RATIONAL ANALYSIS FOR |
| THE BEAM ABOVE THE BUTT GLASS, ECENTRIC |
| LOADING. |
| |
| 8) FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| ROOF FRAMING PLAN MISSING INFORMATION ON |
| ROOF GIRDERS OVER THE COVERED PORCH |
| AREA, SEE VALLEY, MISSING GIRDERS!!!! |
| PROVIDE LOADS! |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |