Plan Review Notes
Plan Review Notes For Permit 03062279
Permit Number 03062279
Review Stop M
Sequence Number 1
Notes
Date Text
2003-07-11 00:00:00DENIED:
  
 1.PLAN SHEET A-1 INDICATES A NEW 1 HR
 FIRE PARTITION WALL.THE MECHANICAL
 PLANS (M2.1) INDICATE EXISTING DUCTWORK
 PENETRATING THIS WALL.A FIRE DAMPER
 WILL BE REQUIRED UNLESS IT COMPLIES WITH
 2001 FBC(M) 607.1.3 #3 ITEMS 1 THROUGH
 4.PLEASE CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.