Plan Review Notes For Permit 03062023 |
Permit Number |
03062023 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2004-08-03 00:00:00 | ********* UNSAT *********** | | | | 1)NOTE: SMOKE DETECTORS ARE REQUIRED | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | ON EACH LEVEL OF A MULTI-LEVEL DWELLING | | UNIT. | | IN CLOSE PROXIMITY OF STAIRWAYS LEADING | | TO FLOORS ABOVE AND IN THE VICINITY OF | | BEDROOMS. | | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE | | A MIN OF 3' FROM BATHROOM DOORS AND | | KITCHENS. | | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 | | MISSING SD ON FIRST FLR LEADING OT FLR | | ABOVE. ALSO NEEDS SD TO BE MOVED INTO | | MASTER BEDROOM. | | | | 2)NOTE: PLEASE SEE MISSING REQUIRED | | LICENSE #'S PER FAC 61G1-16.004 AND | | FS 481.219 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|